18
Fig. 25 — 42DV Unit with Mixing Box Submittal Drawing
NOTES:
1. Right hand unit shown; left hand unit opposite.
2. All dimensions are ± 1/4 in.
3. Product specifications are subject to changes without notice.
4. Dimensions are in inches (mm).
5. Allow adequate spacing or maneuverability around unit to allow service through recommended access area.
6. C dimension is measured from coil side of unit.
7. Mixing box option will vary return duct dimensions, refer to mixing box drawing.
8. Mixing box option includes: a) knockdown base rails which are letter-coded for field assembly, all assembly hardware included; b) pre-assem-
bled mixing box.
9. Linkage kit supplied with Mixing Box is provided for field installation of actuator. Kit consists of 2 crank
arms, 2 swivels, and either a 25 in.
(sizes 06-16) or 34 in.(sizes 20-30) length of 5/16 in. rod.
10. Add 2 in. if using a prefilter or 4 in. filter.
UNIT
SIZE
FAN
SIZE
DEPTH
UNIT
DEPTH
WIDTH HEIGHT
SUPPLY DUCT FLANGES
RETURN
DUCT
FLANGES
MIX
BOX
AUX.
CTRL.
BOX
UNIT SIDE TO
DUCT FLANGE
UNIT BOTTOM TO
DUCT FLANGE
A B C E F H L M N
06 9 x 6 35-1/2 20 28 36-1/2 8-7/8 10-7/8 15-1/8 24 6 11 4-1/2 1-7/8 2-7/8
08 9 x 6 35-1/2 20 28 36-1/2 8-7/8 10-7/8 15-1/8 24 6 11 4-1/2 1 2-7/8
10 9 x 6 39-1/2 22 37 39-3/8 10-1/4 10-7/8 21-1/2 33 8 13 0 1-7/8 2-7/8
12 9 x 6 39-1
/2 22 37 39-3/8 10-1/4 10-7/8 21-1/2 33 8 13 0 1-7/8 2-7/8
16 10 x 7 39-1/2 22 47 39-3/8 13 12 16-5/8 43 8 13 3 1-5/8 2-7/8
20/22 11 x 10 41-1/2 24 48 45-1/8 16-1/4 13 17-1/8 44 8 13 2-1/2 1-7/8 3-1/8
30 12 x 12 47-1/2 28 48 54-1/4 16-1/4 14 16 44 10 15 3-5/8 1-7/8 2-7/8