12
9.3 Dehumidifying mode
9.3.1 Indoor fan speed at low speed.
9.3.2 Protection is same as cooling mode.
9.4 Heating mode
9.4.1 Generally, the 4-way valve is open in heating mode, but it is closed in defrosting mode.
9.4.2 Generally, the outdoor fan is turned off with the on-off action of compressor in heating mode,
except for the defrosting mode or the end of defrost.
9.4.3 Action conditions of compressor at heating mode: compressor must run for 4 minutes after
starting and then judge temperature. Meanwhile other protections are still valid.
Condition Compressor Outdoor fan
T> Ts+4 Off Off Room temp. up
T<Ts+4 On On
T< Ts+3 On On Room temp. down
T>Ts+3 Off Off
9.4.4 Indoor Fan actions at heating mode
Indoor Fan can be set at HIGH/MID/LOW/AUTO by using a remote controller,
Anti-cold wind function 1.
Condition
T= Indoor exchanger temp.
Indoor fan speed
T<TE1 Off
TE1<T<TE2 Low speed
Indoor exchanger temp. up
T>TE2 Setting fan speed
T>TE3 Setting fan speed
TE4<T<TE3 Low speed
Indoor exchanger temp. down
T>TE4 Off
Anti- cold air protection 2 ( when the room temp. satisfy the setting temp.)
T=evaporator pipe sensor temp. Indoor fan speed
T<TE14+2 Low speed or stop Room temp. up
T> TE14+2 Setting speed.
T> TE14 Setting speed. Room temp. down
T< TE14 Stop after 15 seconds Low speed
Auto wind
Condition
T=Indoor Temp.-Setting Temp.
Indoor fan speed
T<2 Med. speed Room temp. up
T>2 Low speed.
T> 0 Low speed. Room temp. down
T<0 Med. speed
Indoor evaporator high-temperature protection
Condition
T= Indoor exchanger temp.
Compressor Outdoor fan
T<TE8 On On
TE8<T<TE7 On Off
Indoor exchanger temp. up
T>TE7 Off Off
T>TE9 Off Off Indoor exchanger temp. down
T<TE9 On On
9.5 Defrosting mode
9.5.1 Conditions of defrost:
Defrosting starts when either of the following :
T3 lower than 0°c, lasts for more than 40 minutes, provided that the time period when the
temperature is lower than -3°c consecutively reaches 3 minutes.