86
42HQG024 + 38YL24 Heating mode
TEMPERATURE
(°C) DRY BULB AIR TEMPERATURE ENTERING
AIR ENTERING OUTDOOR COIL (°C)
INDOOR COIL
-15 -10 -7 -2 2 7 10 15 20
TH 3.76 4.43 4.86 5.65 6.36 7.32 7.76 8.42 8.84
15 THI 3.45 4.06 4.40 5.00 5.51 7.32 7.76 8.42 8.84
KW 1.72 1.81 1.87 1.99 2.11 2.29 2.35 2.47 2.54
TH 3.66 4.32 4.76 5.53 6.24 7.17 7.73 8.45 9.01
20 THI 3.37 3.97 4.31 4.88 5.41 7.17 7.73 8.45 9.01
KW 1.88 1.97 2.03 2.17 2.29 2.48 2.59 2.72 2.84
TH 3.55 4.22 4.64 5.39 6.13 7.04 7.65 8.48 9.27
25 THI 3.26 3.87 4.22 4.76 5.32 7.04 7.65 8.48 9.27
KW 2.05 2.15 2.23 2.36 2.49 2.70 2.83 2.99 3.18