7. Capacity table
7.1 42/38LUVH025N
SUMMER
OUTDOOR TEMPERATURE DRY
Indoor
Conditions
25ºC
30ºC
35ºC
40ºC
45ºC
50ºC
21ºC D
15ºC W
Total capacity W
2477
2356
2192
2013
1848
1724
Sensitive capacity W
1751
1698
1624
1541
1462
1399
Input W.
580
630
680
729
779
829
24ºC D
17ºC W
Total capacity W
2656
2537
2394
2241
2094
1968
Sensitive capacity W
1857
1802
1737
1674
1625
1604
Input W.
581
635
689
742
796
850
27ºC D
19ºC W
Total capacity W
2842
2789
2639
2434
2215
2024
Sensitive capacity W
2012
1970
1895
1804
1712
1633
Input W.
592
648
703
758
813
869
32ºC D
23ºC W
Total capacity W
2895
2942
2900
2800
2669
2537
Sensitive capacity W
1907
1930
1914
1882
1859
1868
Input W.
586
651
716
781
846
910
WINTER
OUTDOOR CONDITIONS
Indoor Conditions
12ºC D
11ºC W
7ºC D
6ºC W
4ºC D
3ºC W
0ºC D
-1ºC W
-4ºC D
-6ºC W
-7ºC D
-8ºC W
15ºC
Capacity W
3435
3057
2703
1747
1461
1408
Input W.
838
748
670
578
537
566
18ºC
Capacity W
3235
2901
2615
1661
1533
1355
Input W.
858
748
682
615
594
622
20ºC
Capacity W
3218
2930
2592
1578
1418
1385
Input W.
881
775
699
615
582
612
22ºC
Capacity W
2992
2850
2473
1339
1433
1337
Input W.
815
769
700
613
586
642