15 Electronic control function 
17.1 Abbreviation 
T1:    Indoor ambient temperature 
T2:    Coil temperature of indoor heat exchanger middle. 
T2B: Coil temperature of indoor heat exchanger outlet(This sensor is located in outdoor unit) 
T3:    Coil temperature of outdoor heat exchanger 
T4:    Outdoor ambient temperature 
T5:    Compressor discharge temperature 
Ts:    Setting temperature 
 
17.2 Electric control working environment. 
17.2.1 Input voltage: 198V~264V. 
17.2.2 Input power frequency:50Hz. 
17.2.3 Indoor fan normal working amp. is less than 1A. 
17.2.4 Outdoor fan. normal working amp. is less than 1.5A. 
17.2.5 Four-way valve normal working amp. is less than 1A. 
 
17.3 Outdoor unit’s digital display tube   
There is a digital display tube in outdoor PCB. 
Digital display tube display function   
 In standby , the LED displays “- -” 
 In compressor operation, the LED display the running frequency, 
 In defrosting mode, The LED displays “dF” or alternative displays between running frequency and    
“dF”(each displays 0.5s) 
 In compressor pre-heating, The LED displays “PH” or alternative displays between running frequency       
and “PH”(each displays 0.5s) 
 During the oil return process, The LED displays “RO” or alternative displays between running     
frequency    and “RO”(each displays 0.5s) 
 In low ambient cooling mode, the LED displays “LC” or alternative displays between running   
frequency    and “LC”(each displays 0.5s) 
 In forced cooling mode, the LED displays “FC” or alternative displays between running frequency    and   
“FC”(each displays 0.5s) 
 When PFC module protection occurs three times within 15 minutes, the LED displays “E6” or           
alternative displays between running frequency    and “E6”(each displays 0.5s) 
 In protection or malfunction, the LED displays error code or protection code.