10. Repairs to sealed components 
10.1    During  repairs  to  sealed  components,  all 
electrical supplies shall be disconnected from the 
equipment being worked upon prior to any removal 
of sealed covers, etc. If it is absolutely necessary to 
have  an  electrical  supply  to  equipment  during 
servicing,  then  a  permanently  operating  form  of 
leak detection shall be located at the most critical 
point to warn of a potentially hazardous situation. 
10.2    Particular  attention  shall  be  paid  to  the 
following to ensure that by working on electrical   
components, the casing is not altered in such a way 
that  the  level  of  protection  is  affected.  This  shall 
include  damage  to  cables,  excessive  number  of 
connections,  terminals  not  made  to  original 
specification, damage  to  seals,  incorrect  fitting  of 
glands,    etc. 
Ensure that apparatus is mounted securely. 
Ensure that seals or sealing materials have not 
degraded  such  that  they  no  longer  serve  the 
purpose  of  preventing  the  ingress  of  flammable 
atmospheres.  Replacement    parts  shall  be  in 
accordance with the manufacturer's specifications. 
NOTE: The  use  of  silicon  sealant may  inhibit the 
effectiveness  of  some  types  of  leak  detection 
equipment.  Intrinsically  safe  components  do  not 
have to be isolated prior to   
working on them. 
11. Repair to intrinsically safe components 
Do  not  apply  any  permanent  inductive  or 
capacitance  loads  to  the  circuit  without  ensuring 
that this will not exceed the permissible voltage and 
current  permitted  for  the  equipment  in  use. 
Intrinsically safe components are the only types that 
can be worked on while live in the presence of a 
flammable atmosphere. The test apparatus shall be 
at the correct rating.   
Replace  components only  with  parts  specified  by 
the manufacturer. Other parts may result   
in the ignition of refrigerant in the atmosphere from 
a leak. 
12. Cabling 
Check  that  cabling  will  not  be  subject  to  wear, 
corrosion,  excessive  pressure,  vibration,  sharp 
edges or any other adverse environmental effects. 
The check shall also take into account the effects of 
aging or continual vibration from sources such as 
compressors or fans. 
13. Detection of flammable refrigerants 
Under no circumstances shall potential sources of 
ignition be used in the searching for or detection of 
refrigerant  leaks.  A  halide  torch  (or  any  other 
detector using a naked flame)   
shall not be used. 
14. Leak detection methods 
The following leak detection methods are deemed 
acceptable for systems containing   
flammable  refrigerants.  Electronic  leak  detectors 
shall be used to detect flammable   
refrigerants, but the sensitivity may not be adequate, 
or  may  need  re-calibration.  (Detection  equipment 
shall  be  calibrated  in  a  refrigerant-free  area.) 
Ensure that the detector is not a potential source of 
ignition and is suitable for the refrigerant used. Leak 
detection equipment shall be set at a percentage of 
the LFL of the refrigerant and shall be calibrated to 
the  refrigerant  employed  and  the  appropriate 
percentage of gas (25 % maximum) is confirmed. 
Leak detection fluids are suitable for use with most 
refrigerants  but  the  use  of  detergents  containing 
chlorine shall be avoided as the chlorine may react 
with  the  refrigerant  and  corrode  the  copper 
pipe-work.   
If a leak is suspected, all naked flames shall be 
removed or extinguished. 
If a leakage of refrigerant is found which requires 
brazing, all of the refrigerant shall be   
recovered from the system, or isolated (by means 
of shut off valves) in a part of the system 
remote from the leak. Oxygen free nitrogen (OFN) 
shall  then  be  purged  through  the  system  both 
before and during the brazing process. 
15. Removal and evacuation 
When breaking into the refrigerant circuit to make 
repairs    or for any other purpose   
conventional procedures shall be used. However, it 
is important that best practice is   
followed since flammability is a consideration. The 
following procedure shall be adhered to: 
remove refrigerant; 
purge the circuit with inert gas; 
evacuate; 
purge again with inert gas; 
open the circuit by cutting or brazing. 
The refrigerant charge shall be recovered into the 
correct recovery cylinders. The system   
shall be      flushed        with OFN to render the unit 
safe.  This  process  may  need  to  be  repeated 
several times. Compressed air or oxygen shall not 
be used for this task. Flushing shall be achieved by 
breaking the vacuum in the system with OFN and 
continuing  to  fill  until  the  working  pressure  is 
achieved, then venting to atmosphere, and finally 
pulling  down  to  a  vacuum.  This process  shall  be 
repeated until  no refrigerant  is  within  the system. 
When  the  final  OFN  charge  is  used,  the  system 
shall  be  vented down  to atmospheric pressure  to 
enable  work  to  take  place.  This  operation  is 
absolutely  vital  if  brazing  operations  on  the 
pipe-work are to take place. 
Ensure that the outlet for the vacuum pump is not 
close to any ignition sources and there is   
ventilation available. 
16. Charging procedures