APPENDIX B (cont)
INPUT/OUTPUT TABLES — CHANNELS 31-48 (PSIO2) — SIZES 088 AND 104
INPUT/OUTPUT TABLES — CHANNELS 49-60 (DSIO2) — SIZES 088 AND 104
LEGEND
*Thermistor voltage signals varies according to temperature at
thermistor; see Thermistor Characteristic Tables 59 and 60 for
correlation of temperature and volts at these channels.
†When accessory transducer/sensor package has been installed
(requires changes in “Factory Configuration” inputs).
**Use relay HK35AB-001 (SPDT — pilot duty) for external control.
††Field-connection from building/energy management system.
||Field-connection to room terminal heating interlock
PSIO2 TERMINAL ID SIGNAL
TYPE ASSIGNMENT
Channel
No.
+ Type Level
Inputs
31
J7-2 J7-3 Analog Varies* Thermistor, 5K STATHERM — Suction Gas Thermistor, Circuit A
32
J7-5 J7-6 Analog Varies* Thermistor, 5K STBTHERM — Suction Gas Thermistor, Circuit B
33
J7-7 J7-8 Analog 2-10 vdc Analog OARHV — Outdoor Relative Humidity
34
J7-10 J7-11 Analog 2-10 vdc Analog RHV — Space/Return Relative Humidity
35
J7-13 J7-14 Analog 2-10 vdc Analog OACV — Outdoor Air Cfm
36
J7-16 J7-17 Analog 2-10 vdc Analog IAQV — Indoor Air Quality
37
J7-19 J7-32 Discrete 24 vac Contact, NO PRES — Pressurization
38
J7-22 J7-32 Discrete 24 vac Contact, NO PURG — Smoke Purge
39
J7-25 J7-32 Discrete 24 vac Contact, NO EVAC — Evacuation
40
J7-28 J7-32 Discrete 24 vac Contact, NO FSD — Fire Shutdown
41
J7-31 J7-32 Discrete 24 vac Contact, NO FRZ — Freezestat
42
J7-34 J7-35 Analog 2-10 vdc Analog SATRV — Supply Air Reset
Outputs
43
J6-37 J6-38 Analog 10 vdc Proportional, 4-20 mA HCVOUT — Heating Coil Valve
44
J6-42 J6-41 Discrete 20 vac Contact, NO** DTCC — Discrete Time Clock Control
45
J6-43 J6-44 Analog 10 vdc Proportional, 4-20 mA HUMOUT — Analog Humidifier
J6-45 J6-44 Discrete 20 vdc Contact, NO** HUMOUT — Discrete Stage Humidifier
46
J6-48 J6-47 Discrete 24 vac Contact, NO
MMB — Motormaster
®
Control/Outdoor Fan Stage 1, Circuit B
47
J6-51 J6-50 Discrete 24 vac Contact, NO MMA — Motormaster Control/Outdoor Fan Stage 1, Circuit A
48
J6-54 J6-53 Discrete 24 vac Contact, NO ALERTLT — Alert Light
DSIO2 TERMINAL ID SIGNAL
TYPE ASSIGNMENT
Channel
No.
+ Type Level
Inputs
49
J3-1 J3-2 Discrete 24 vac** Discrete EXTCLK — Remote Start/Stop
50
J3-3 J3-4 (Not Used)
51
J3-5 J3-6 Discrete 24 vac Contact Set CPFA2 — Compressor A2 Safety
52
J3-7 J3-8 Discrete 24 vac Contact Set CPFB1 —Compressor B2 Safety
Outputs
53
J4-3 J4-2 Discrete 115 vac Contact, NO CMPA2 — Compressor A2
J4-3 J4-1 Discrete 115 vac Contact, NC CCHA2 — Compressor A2
54
J4-6 J4-5 Discrete 115 vac Contact, NO CMPB2 — Compressor B2
J4-6 J4-4 Discrete 115 vac Contact, NC CCHB2 — Compressor B2
55
J4-9 J4-8 Discrete 24 vac Contact, NO ULDA2 — Unloader A2
56
J4-12 J4-11 Discrete 24 vac Contact, NO UNLB2 — Unloader B2
57
J5-3 J5-2 Not Used
58
J5-6 J5-5 Not Used
59
J5-9 J5-8 Discrete 115 vac†† Contact, NO
Alarm, Discrete (Field Connection)
J5-9 J5-7 Discrete 115 vac†† Contact, NC
60
J5-12 J5-11 Discrete 115 vac|| Contact, NO
HIR — Heat Interlock Relay (Field Connection)
J5-12 J5-10 Discrete 115 vac|| Contact, NC
HIR
Heat Interlock Relay
IGV
Inlet Guide Vanes
NC
Normally Closed
NO
Normally Open
VAV
Variable Air Volume
UNIT SIZE 088,104
HIR Contact
TB2
N.O.
8 + 9
N.C.
8 + 10