105
APPENDIX B
INPUT/OUTPUT TABLES — CHANNELS 1-18 (PSIO1) — SIZES 088 AND 104
INPUT/OUTPUT TABLES — CHANNELS 19-30 (DSIO1) — SIZES 088 AND 104
LEGEND
*Thermistor voltage signals varies according to temperature at
thermistor; see Thermistor Characteristic Tables 59 and 60 for
correlation of temperature and volts at these channels.
†When accessory transducer/sensor package has been installed
(requires changes in “Factory Configuration” inputs).
**Use relay HK35AB-001 (SPDT — pilot duty) for external control.
††Field-connection from building/energy management system.
||Field-connection to room terminal heating interlock.
PSIO1 TERMINAL ID SIGNAL
TYPE ASSIGNMENT
Channel
No.
+ – Type Level
Inputs
1
J7-2 J7-3 Analog Varies* Thermistor, 5K SAT — Supply-Air Temperature
2
J7-5 J7-6 Analog Varies* Thermistor, 5K RAT — Return-Air Temperature
3
J7-8 J7-9 Analog Varies* Thermistor, 5K
STHA — Saturated Condensing Temperature, Circuit
A
J7-8† J7-7 Analog 1-5 vdc Transducer, Pressure DPAV — Discharge Pressure Transducer, Circuit A
4
J7-11 J7-12 Analog Varies* Thermistor, 5K
STHB — Saturated Condensing Temperature, Circuit
B
J7-11† J7-10 Analog 1-5 vdc Transducer, Pressure DPBV — Discharge Pressure Transducer, Circuit B
5
J7-13
J7-14
Discrete 24 vac Contact Set LPA — Low-Pressure Switch, Circuit A
J7-13† Analog 1-5 vdc Transducer, Pressure SPAV — Suction Pressure Transducer, Circuit B
6
J7-16 J7-17 Discrete 24 vac Contact Set LPB — Low-Pressure Switch, Circuit B
J7-16† J7-17 Analog 1-5 vdc Transducer, Pressure SPBV — Suction Press Transducer, Circuit B
7
J7-20 J7-21 Analog Varies* Thermistor, 5K OAT — Outdoor-Air Temperature
8
J7-23 J7-24 Analog Varies* Thermistor, 10K SPTSNSR —Space Temperature
9
J7-25 J7-26 Analog 2-10 vdc Transducer, Pressure BP — Building Pressure
10
J7-28 J7-29 Discrete 24 vac Contact Set ENTH — Enthalpy Switch
11
J7-31
J7-32
Analog 2-10 vdc Transducer, Pressure SP — Duct Static Pressure (VAV)
J7-33 Analog 2-10 vdc Thermistor, 10K STOTHERM — Space Temperature Offset/T-56
12
J7-35
J7-36
Discrete 5 vdc Contact Set FLTS — Filter Status
Pin 36 Discrete 10 vdc Contact Set SFS — Supply Fan Status
Outputs
13
J6-37 — — — — Not Used
14
J6-40 — Analog 10 vdc Proportional, 4-20 mA ECON — Economizer Damper Position
15
J6-43 — Analog 10 vdc Porportional, 4-20 mA PED — Power Exhaust Damper Position
16
J6-46 J6-47 Analog 10 vdc Proportional, 4-20 mA INV — Inverter/IGV (VAV)
17
J6-51 J6-50 Discrete 24 vac Contacts (NO) HS1 — Heat Stage 1
18
J6-54 J6-53 Discrete 24 vac Contacts (NO) HS2 — Heat Stage 2
DSIO1 TERMINAL ID SIGNAL
TYPE ASSIGNMENT
Channel
No.
+ – Type Level
Inputs
19
J3-1 J3-2 Discrete 24 vac Contact Set CPFA1 — Compressor A1 Safety
20
J3-3 J3-4 Discrete 24 vac Contact Set CPFB1 — Compressor B1 Safety
21
J3-5 J3-6 Discrete 24 vac Contact Set CPSA1 — Compressor A1 Status
22
J3-7 J3-8 Discrete 24 vac Contact Set CPSA1 — Compressor A1 Status
Outputs
23
J4-3 J4-2 Discrete 115 vac Contact Set (NO) CMPA1 — Compressor A1
J4-3 J4-1 Discrete 115 vac Contact Set (NC) CCHA1 — Crankcase Heater A1
24
J4-6 J4-5 Discrete 115 vac Contact Set (NO) CMPB1 — Compressor B1
J4-6 J4-4 Discrete 115 vac Contact Set (NC) CCHB1 — Crankcase Heater B1
25
J4-9 J4-8 Discrete 24 vac Contact Set (NO) ULDA1 — Unloader A1
26
J4-12 J4-11 Discrete 24 vac Contact Set (NO) UNLB1 — Unloader B1
27
J5-3 J5-2 Discrete 115 vac Contact Set (NO) SPF — Supply Fan Contactor
28
J5-6 J5-5 Discrete 115 vac Contact Set (NO) EF — Exhaust Fan Contactor
29
J5-9 J5-8 Discrete 115 vac Contact Set (NO) OFA — Outdoor Fan Contactor, Circuit A
30
J5-12 J5-11 Discrete 115 vac Contact Set (NO) OFB — Outdoor Fan Contactor, Circuit B
HIR —
Heat Interlock Relay
IGV —
Inlet Guide Vanes
NC —
Normally Closed
NO —
Normally Open
VAV —
Variable Air Volume
UNIT SIZE 088,104
HIR Contact
TB2
N.O.
8 + 9
N.C.
8 + 10