Table 68 — Service Directory (cont)
SERVICE (cont)
Subfunction Keypad Entry Display Description
6
USER
CONFIGURATION
USER CFG User configuration
HUSN X
Humidity sensors (0 = None, 1 = Differential [2 Sensors],
2 = Space Override [1 Sensor])
SUSN X Suction sensors (0 = No, 1 = Yes)
VENT X Ventilation control (0 = MDP, 1 = IAQ, 2 = CFM, 3 = All)
MMAS X Motormaster (0 = No, 1 = Yes)
PURG X Indoor-air quality (0 = Disable, 1 = Enable)
NTEN X Nighttime free cool (0 = Double, 1 = Enable)
OSEN X Adaptive optimal start/stop (0 = Disable, 1 = Enable)
DLEN X Demand limit (0 = Disable, 1 = Enable)
OHEN X Occupied heating (0 = Disable, 1 = Enable)
RSEN X Space temperature reset (0 = Disable, 1 = Enable)
DPEN X Duct pressure control (0 = Disable, 1 = Enable)
FANM X Fan mode auto/cont (0 = Auto, 1 = Cont)
TSCH X Timed override schedules (1 = Unit, 2 = DTCC, 3 = Both)
TOVR X Timed override value (0 to 4 hours)
LLAG X Lead/Lag option (0 = Disable, 1 = Enable)
7
HEATING
COIL
HEATCOIL Configure heating coil
MLG X Master loop gain value
SMG X Submaster gain value
SCV X Submaster center value
FOV X Fan off value (F)
SMR X Submaster reference value
X*
SMR X Submaster reference value forced (35 to 140 F)
8
COOLING
COOLING Configure cooling parameters
MLG X Master loop gain value
HHL X High humidity limit (0 to 99%)
9
DUCT
PRESSURE
DUCTPRES Configure duct pressure control
MLG X Master loop gain value
SMG X Submaster gain value
SCV X Submaster center value
SMR X Submaster reference value
X*
SMR X Submaster reference value forced (0.0 to 5.0 in. wg)
10
ECONOMIZER
ECONMIZR Configure economizer
MLG X Master loop gain value
SMG X Submaster gain value
SCV X Submaster center value
MDP X Minimum damper position (percent open)