123
APPENDIX D: SystemVut Controller CCN Tables
Maintenance Tables (cont)
Tab le Display Name Range Units Point Name
Write
Status
COOLDIAG (cont)
cmp Loader Timeguard xxx sec TIMG_ALD
Compressor A1 locked out Yes/No CA1_LOCK
Compressor A2 locked out Yes/No CA2_LOCK
Compressor A1 Available Ye s/No CA1_AVAL
Compressor A2 Available Ye s/No CA2_AVAL
Recent Comp A1 Strike Yes/No A1STKACT
Recent Comp A2 Strike Yes/No A2STKACT
Circuit A Compressor 1 On/Off COMP_A1
Circuit A Compressor 2 On/Off COMP_A2
Circuit A CMP A1 Loader On/Off COMP_ALD
Actual Cool Stage Active x ACTCSTGS
Ok to Dehumidify? Yes/No OKTODHUM
Humidimizer Lockout Temp --- 20 to 75 °F OATLHUMZ
Ok to fan based dehum Yes/No OKTOFBD
Ok to use humidimizer Yes/No OKTOHUMZ
Req Compr DehumStgs 0to3 REQDSTGS
Request ed Dehum Level 0to2 REQDSTGS
Liquid Dischg Valve CirA Enable/Disable LDV_A
Reheat Dischg Valve CirA Enable/Disable RDV_A
High Pressure Override Yes/No HP_OVR
ODF Speed Signal Output1 0 to 1200 rpm ODF1SPD
ODF Speed Signal Output2 0 to 1200 rpm ODF2SPD
ODF Speed Signal Output3 0 to 1200 rpm ODF3SPD
ODF Control SDT SP 0 °F ODFSDTSP
Low Ambient Ctrl Status 0=Normal,
1=Entering,
2=Low Ambient,
3=Exiting
LACTRLST
Outdoor Air Temperature xxx.x °F OAT Forcible
FBDH SST locked out Ye s/No FBDSSTLO
FBDH SAT Lockout Yes/No FBDSATLO
Cir.A High Pressure Sw Open/Close CIRA_HPS
Cir .A Discharge Pressure xxx.x psig SDP_A
Cir .A Suction Pressure xxx.x psig SSP_A
Circuit A Pressure Ratio xx.xx CIRA_PR
Cir.A Sat.Discharge Temp xxx.x °F SDT_A
Cir.A Sat.Suction Temp xxx.x °F SST_A
HUMZDIAG
Ok to Dehumidify? Yes/No OKTODHUM
Request ed Dehum Level 0to2 REQDHLEV
Ok to use humidimizer Yes/No OKTOHUMZ
Liquid Dischg Valve CirA Enable/Disable LDV_A
Reheat Dischg Valve CirA Enable/Disable RDV_A
Reheat Liquid Valve CirA Enable/Disable RLV_A
Cooling Liq Valve CirA Enable/Disable CLV_A
Fan Based Dehum Type 0=None,
1=Comfort,
2=Max
FBD_TYPE
FBDH SAT Min value 35 to 80 °F FBDH_ SAT
FBDH SST Min value 10 to 60 °F FBDH_SST
FBDH Low Set Point --- 2 0 t o 0 °Fdelta FBDLO_SP
Request ed IDF Speed 0 t o 200 % RQFANSPD
Ok to fan based dehum Yes/No OKTOFBD
FBDH SST locked out Ye s/No FBDSSTLO
FBDH SAT Lockout Yes/No FBDSATLO
OKFCDIAG
Outdoor Air Temperature xxx.x °F OAT Forcible
OA Relative Humidity 0 to 100 % OARH Forcible
Outdoor Air Enthalpy xxx.x Btu/lb OA_ENTH Forcible
Return Air Te mpe rature xxx.x °F RAT Forcible
RA Relative Humidity 0 to 100 % RARH Forcible
Return Air Enthalpy xxx.x Btu/lb RA_ENTH Forcible
Barometric Pressure xx.xx in.Hg BARP Forcible