Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53480279-01 Printed in U.S.A. Form 48LC-4-6-02SM Pg 1 2-2020 Replaces: 48LC-4-6-01SM
Service and Maintenance Instructions
TABLE OF CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . 1
UNIT ARRANGEMENT AND ACCESS . . . . . . . . . . . . 3
Routine Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . 3
Seasonal Maintenance . . . . . . . . . . . . . . . . . . . . . . . . 3
SUPPLY FAN (BLOWER) SECTION . . . . . . . . . . . . . . 4
Supply Fan (Belt-Drive) . . . . . .
. . . . . . . . . . . . . . . . . 4
COOLING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Condenser Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Condenser Coil Maintenance and Cleaning
Recommendation . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Evaporator Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Refrigerant System Pressure
Access Ports . . . . . . . 7
Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Filter Drier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Condenser-Fan Adjustment . . . . . . . . . . . . . . . . . . . . 8
Troubleshooting Cooling System . . . . . . . . . . . . . . . 8
PURON® (R-410A) REFRIGERANT . . . . . . . . . . . . . 10
Refrigerant Charge . . . . .
. . . . . . . . . . . . . . . . . . . . . 10
COOLING CHARGING CHARTS . . . . . . . . . . . . . . . . 11
THERMOSTATIC EXPANSION VALVE (TXV) . . . . . 14
TXV Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
CONVENIENCE OUTLETS . . . . . . . . . . . . . . . . . . . . 14
Non-Powered Type . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Unit-Powered Type . . . . . . . . . . . . .
. . . . . . . . . . . . . 14
SMOKE DETECTORS . . . . . . . . . . . . . . . . . . . . . . . . 15
System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Smoke Detector Locations . . . . . . . . . . . . . . . . . . . . 16
Completing Installation of Return Air Smoke
Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
FIOP Smoke Detector Wiring and Response . . . . . 17
Sensor and Controller Tests . . . . . . . . . . . . . . . . . . 18
Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Resetting Alarm and Trouble Condition Trips . . . . 21
Troubleshooting . . . . . .
. . . . . . . . . . . . . . . . . . . . . . 21
PROTECTIVE DEVICES . . . . . . . . . . . . . . . . . . . . . . 21
Compressor Protection . . . . . . . . . . . . . . . . . . . . . . 21
Supply (Indoor) Fan Motor Protection . . . . . . . . . . 21
Relief Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Control Circuit, 24-V . . . . . . . . . . . . . . . . . . . . . . . . . 21
GAS HEATING
SYSTEM . . . . . . . . . . . . . . . . . . . . . . 21
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Fuel Types and Pressures . . . . . . . . . . . . . . . . . . . . 22
Flue Gas Passageways . . . . . . . . . . . . . . . . . . . . . . . 23
Combustion-Air Blower . . . . . . . . . . . . . . . . . . . . . . 23
Burners and Igniters . . . . . . . . . . . . . . . . . . . . . .
. . . 24
Burner Ignition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Orifice Replacement . . . . . . . . . . . . . . . . . . . . . . . . .26
Minimum Heating Entering Air Temperature . . . . . .26
Troubleshooting Heating System . . . . . . . . . . . . . . .26
PRE-START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
START-UP, GENERAL . . . . . . . . . . . . . . . . . . .
. . . . .32
Unit Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
Return-Air Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
Outdoor-Air Inlet Screens . . . . . . . . . . . . . . . . . . . . .33
Compressor Mounting . . . . . . . . . . . . . . . . . . . . . . . .33
Internal Wiring .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
Refrigerant Service Ports . . . . . . . . . . . . . . . . . . . . .33
Compressor Rotation . . . . . . . . . . . . . . . . . . . . . . . .33
Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
Main Burners . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
Heating . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .33
Ventilation (Continuous Fan) . . . . . . . . . . . . . . . . . .33
Electrical Connections . . . . . . . . . . . . . . . . . . . . . . .33
RTU Open Control System . . . . . . . . . . . . . . . . . . . .35
SystemVu™ (Factory Option) . . . . . . . . . . . . . . . . . .35
Economi$er® X (Factory Option) . . . . . . . . . . . . . . .35
VFD OPERATION WITH REMOTE KEYPAD . . . . . . .46
To Connect the VFD Keypad using the RJ
-45
Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46
Start Up with Assistant . . . . . . . . . . . . . . . . . . . . . . .46
Start Up by Changing Parameters Individually . . . .47
VFD Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
Fan Speed Relay Board . . . . . . . . . . . . . . . . . . . . . . .58
Configuration Jumpers . . . . . . . . . . . .
. . . . . . . . . . .58
Variable Frequency Drive . . . . . . . . . . . . . . . . . . . . .58
FASTENER TORQUE VALUES . . . . . . . . . . . . . . . . .60
APPENDIX A MODEL NUMBER
NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . . . .61
APPENDIX B PHYSICAL DATA . . . . . . . . . . . . . . .62
APPENDIX C FAN DATA . . . . . . . . . . . . . . . . . . . .63
APPENDIX D WIRING DIAGRAMS . . . . .
. . . . . . .71
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . .CL-1
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be
hazardous due to system pressure and electrical components. Only
trained and qualified service personnel should install, repair, or
service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of
cleaning coils and filters and replacing filters. All other operations
should be performed by trained service personnel. When working
on air-conditioning equipment, observe precautions in the
literature, tags and labels attached to the unit, and other safety
precautions that may apply.
Follow all safety codes, including ANSI (American National
Standards Institute) Z223.1. Wear safety glasses and work gloves.
WeatherExpert
®
48LC 04-06
Single Package Rooftop
Gas Heating/Electric Cooling Unit
with Puron
®
(R-410A) Refrigerant

Table of Contents

Questions and Answers:

Carrier WeatherExpert 48LCE05 Specifications

General IconGeneral
Phase1
RefrigerantR410A
Weight35 kg
Sound Level50 dB
Operating Temperature (Heating)Not applicable (Cooling Only)
Noise Level (Outdoor)50 dB
Dimensions (Indoor Unit)800 x 300 x 550 mm
Weight (Outdoor Unit)35 kg

Summary

Safety Considerations

Cooling System Maintenance

Condenser Coil Cleaning

Provides recommendations for cleaning condenser coils.

Puron® (R-410A) Refrigerant Handling

Refrigerant Charge and Cooling Charts

Details refrigerant charge amount and procedures using cooling charts.

General Safety Warnings

Signal Words and Hazard Identification

Explains signal words used for safety information.

Gas Hazard Precautions

Warns about gas hazards and safe practices.

Electrical Hazard Precautions

Warns about electrical hazards and lockout/tagout procedures.

R-410A System Safety

Highlights safety for R-410A systems due to higher pressures.

Cooling System Components

Condenser Coil Maintenance

Provides recommendations for cleaning condenser coils.

Heating Service Analysis

Burners Will Not Ignite

Troubleshooting steps for when burners will not ignite.

IGC Board LED Alarm Codes

Pre-Start-Up Procedures

Personal Injury and Environmental Hazards

Safety warnings for personal injury and environmental hazards.

Electrical Operation Hazard

Safety warnings related to electrical hazards during pre-start-up.

Start-Up, General

Economizer Controls

Economi$er® X (Factory Option)

Information on the EconoMi$er X system.

W7220 Economizer Module Interface

Setup and Configuration

Steps for setting up and configuring the economizer module.

W7220 Menu Structure

Advanced Setup Menu

Checkout Procedures

VFD Operation Troubleshooting

VFD Operation with Remote Keypad

Connecting and using the VFD keypad remotely.

VFD Parameter Management

Changing Parameters Individually

Procedure for changing VFD parameters individually.

VFD Diagnostics

Fault Indicators and Correction

Indicators and behavior for severe faults and corrective actions.

Fan Speed Relay Board

Variable Frequency Drive (VFD) Integration

Explanation of the VFD's role and capabilities with the fan board.

Appendix A - Model Number Nomenclature

Appendix B - Physical Data

Appendix C - Fan Data

Appendix D - Wiring Diagrams

Start-Up Checklist

Pre-Start-Up Procedures

Pre-start-up checks to ensure proper installation and readiness.

Start-Up Electrical and Temperature Checks

Electrical and temperature checks during initial start-up.

Pressures and Humidi-Mizer® Start-Up

Humidi-Mizer® System Start-Up Steps

Steps for performing the Humidi-Mizer start-up.