APPENDIX D: SystemVut Controller CCN Tables
Maintenance Tables (cont)
Tab le Display Name Range Units Point Name
Write
Status
PE_DIAG (cont)
P.Exhaust 1 Curve Offset 0 to 100 % PE1_OFFS
P.Exhaust 2 Curve Offset 0 to 100 % PE2_OFFS
P o w e r E x h a u s t 1 --- S p e e d 1 0 to 100 % PE1_SPD1
P o w e r E x h a u s t 1 --- S p e e d 2 0 to 100 % PE1_SPD2
P o w e r E x h a u s t 1 --- S p e e d 3 0 to 100 % PE1_SPD3
PE Stage 1 at Max speed 0 to 100 % PE1_PMAX
Power Exhaust 1 --- Pos 1 0 t o 100 % PE1_POS1
Power Exhaust 1 --- Pos 2 0 t o 100 % PE1_POS2
Power Exhaust 1 --- Pos 3 0 t o 100 % PE1_POS3
P o w e r E x h a u s t 2 --- S p e e d 1 0 to 100 % PE2_SPD1
P o w e r E x h a u s t 2 --- S p e e d 2 0 to 100 % PE2_SPD2
P o w e r E x h a u s t 2 --- S p e e d 3 0 to 100 % PE2_SPD3
PE Stage 2 at max speed 0 to 100 % PE2_PMAX
Power Exhaust 2 --- Pos 1 0 t o 100 % PE2_POS1
Power Exhaust 2 --- Pos 2 0 t o 100 % PE2_POS2
Power Exhaust 2 --- Pos 3 0 t o 100 % PE2_POS3
VENTDIAG
O p e r a t i n g S u b --- M o d e see Appendix B SUBMTEXT
Ventilation Status see Appendix B VENTTEXT
Ventilation Status see Appendix B VENTSTAT
Currently Occupied Yes/No OCCUPIED Forcible
Mins until next occupied xxxxx min MINTILOC
FanOnWhenOccupied Yes/No FANON_OC
IDF Commanded RPM RPM FSPD_RPM
Free Co oling active Yes/No FREECOOL
MinPositioninEffect 0 to 100 % MIN_POS Forcible
Requested Damper Pos 0 to 100 % REQDAMP
Econo Commanded Position 0 to 100 % DAMPCMD Forcible
Econo Actual Position 0 t o 100 % DAMPPOS Forcible
Analog Input IAQ Control 0=NO IAQ,
1=DCV,
2=IAQ OVRD,
3=CTRL MINP
IAQANCFG
Indoor Air Quality Level xxxx PPM IAQ Forcible
OA Quality Level xxxx PPM OAQ Forcible
Differential Air Quality xxxx PPM AQ_DIFF
AQ Differential High xxxx PPM DAQ_HIGH
AQ Differential Low xxxx PPM DAQ_LOW
AQ Diff High IAQOVERRIDE 0 to 5000 PPM AQD_HIGH
AQ Diff Low --- IAQ OVERRIDE 0 to 5000 PPM AQD_LOW
IAQ override enable Yes/No IAQOVREN
IAQ Preoccupancy Purge Yes/No IAQPURGE
Preocc Purge Lockout OAT 0to70 °F IAQP_LA
Ok to Preoccupancy Purge Yes/No OKPREOCC
Preocc Purge Duration 5 to 120 min IAQPTIME
In Pre--- Occupancy Purge? Yes/No PREOCCON
Is IAQ Override Active? Yes/No IAQ_OVRD
IAQ override sw state Yes/No IAQ_OVRS
Economizer Installed? Yes/No ECONO
2 Pos or ERV Channel EV2PCHAN
Supply Air Temperature xxx..x °F SAT
Return Air Te mpe rature xxx.x °F RAT Forcible
Outdoor Air Temperature xxx.x °F OAT Forcible
Damper SAT deadband 0to20 °F T24SATDB
T24 Min Diff in RAT--- OAT 5to20 °F T24RATDF