APPENDIX D: SystemVut Controller CCN Tables
Maintenance Tables (cont)
Tab le Display Name Range Units Point Name
Write
Status
LINKDATA
Linkage CCN element # xxx LNK_SUPE Forcible
Linkage CCN Bus number xxx LNK_SUPB Forcible
Block No: in Master Zone 1to8 LNK_MZBK Forcible
Average Occup. Heat Stp. xxx.x °F LNK_OHSP Forcible
Average Occup. Cool Stp. xxx.x °F LNK_OCSP Forcible
Average Unocc. Heat Stp. xxx.x °F LNK_UHSP Forcible
Average Unocc. Cool Stp. xxx.x °F LNK_UCSP Forcible
AverageZoneTemperature xxx.x °F LNK_AZT Forcible
Average Occup. Zone Temp xxx.x °F LNK_AOZT Forcible
Linkage Occupied Request 0=Unocc,
1=Occupied,
2=Disabled
LNK_OCC Forcible
Linkage Next Occ Day text string LNEXTOCD
Linkage Next Occ Time hh:mm LNEXTOCT
Linkage Last Unocc Day text string LNEXTUOD
Linkage Next Unocc Time hh:mm LNEXTUCT
Linkage Last Unocc Day text string LLASTUOD
Linkage Last Unocc Time hh:mm LLASTUCT
Linkage Active Yes/No LNK_ACT Forcible
Linkage Equipment Mode 1to8 LNK_MODE Forcible
Linkage Start Bias time xxx min LNK_SBT Forcible
Value of Prime variable xxx.x °F PRIME_V
OCC_DIAG
Currently Occupied Yes/No OCCUPIED Forcible
Active Occupancy control 0=24/7OCC,
1=Schedule,
2=BASCTRL,
3=REMOCCTL,
4 = Time Override,
5=Linkage,
6=Forced
OCC_CTRL
Linkage Occupied Request 0=Unocc,
1=Occupied,
2=Disabled
LNK_OCC Forcible
Timed Override Remaining 0 to 240 min OVR_EXT Forcible
Remote Occupancy Switch On/Off REMOCC Forcible
BMS Occupancy Request 0=Unocc,
1=Occupied,
2=Disabled
BMS_OCC Forcible
Local Sched Occ Request 0=Unocc,
1=Occupied
LOC_OCC Forcible
Active Schedule period 0to8 PER_NO
Mins until next occupied --- 1 t o 10080 min MINTILOC
BACnet Cal Object Status Yes/No CALOBJST
Today Is A Holiday Yes/No HOLTODAY
Tomorrow Is A Holiday Yes/No HOL_TMRW
Next Occupied Day DDD NXTOCDAY
Next Occupied Time hh:mm NXTOCTIM
Next Unoccupied Day DDD NXTUNDA Y
Next Unoccupied Time hh:mm NXTUNTIM
Previous Unccupied Day DDD PRVUNDAY
Previous Unoccupied Time hh:mm hh.mm PRVUNTIM
Accept Global Holidays? Ye s/No HOLIDAYT
Global Schedule Broadcst Yes/No CCN_GSBC
CCN Schedule Number 0to99 SCHEDNUM
0 = Always Occupied
1 --- 6 4 = L o c a l S c h e d u l e
65--- 99 = Global Schedule
Remote Occupancy Channel 0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04
RMOCCHAN
Remote Occupancy Switch On/Off REMOCC Forcible
Timed Override Duration 0to4 hours OTL_CFG
BAS Proto col Select 0=NONE,
1=CCN,
2=BACNET
BMS_CFG