APPENDIX D: SystemVut Controller CCN Tables
Service Config Tables (cont)
Tab le N am e Display Name Range Units Point Name Default
ECON_CFG (co nt)
PE Turn Off Dead band 0 t o 100 % PE_OFFDB 5
PE2 Relay Channel 0=NONE,
1=MBB RLY11,
2=MBB RLY06
PE2_CHAN 0=None
PE Stage 2 at max speed 0 t o 100 % PE2_PMAX 75
T24 Heat/Cool End Delay 0to60 min T24CHDLY 25
T24Econ Min Move for SAT 10 to 20 % T24ECSTS 10
Damper SAT deadband 0to20 °F T24SATDB 12
T24 Min Diff in RAT--- OAT 5to20 °F T24RATDF 15
T24 Test Minimum Pos 0 to 100 % T24TSTMN 15
T24 Test Maximum Pos 0 t o 100 % T24TSTMX 85
IAQ_CFG
Analog Input IAQ Control 0to3 IAQANCFG 0: no FIOP
1: FIOP
0=NoIAQ
1=DCV
2 = IAQ Override
3=MINPOSControl
IAQ Position at Max Fan 0 to 100 % IAQMINP 10
AQ Differential Low 0 t o 5000 ppm DAQ_LOW 100
AQ Differential High 0 t o 5000 ppm DAQ_HIGH 700
IAQ Preoccupancy Purge Yes/No IAQPURGE Ye s
IAQ Purge Pos at Max IDF 0 t o 100 % IAQPMAX 40
Preocc Purge Lockout OAT 0to70 °F IAQP_LA 50
Preocc Purge Duration 5 t o 120 min IAQPTIME 15
IAQ Sensor Value at 4mA 0 to 5000 ppm IAQ_4MA 0
IAQ Sensor Value at 20mA 0 to 5000 ppm IAQ_20MA 2000
OAQ Sensor Value at 4mA 0 to 5000 ppm OAQ_4MA 0
OAQ Sensor Value at 20mA 0 to 5000 ppm OAQ_20MA 2000
IAQ override sw channel 0to6 IAQOCHAN
IAQ Override Switch Type Yes/No IAQOSCFG
USER_INS
Supply Voltage Leg 1 0 t o 700 volts L1VOL TS
Supply Voltage Leg 2 0 t o 700 volts L2VOL TS
Supply Voltage Leg 3 0 t o 700 volts L3VOL TS
Comp A1 Amps Leg 1 0 to 100 Amps CA1L1_A
Comp A1 Amps Leg 2 0 to 100 Amps CA1L2_A
Comp A1 Amps Leg 3 0 to 100 Amps CA1L3_A
Comp A2 Amps Leg 1 0 to 100 Amps CA2L1_A
Comp A2 Amps Leg 2 0 to 100 Amps CA2L2_A
Comp A2 Amps Leg 3 0 to 100 Amps CA2L3_A
Elec. Heat Amps Leg 1 0 t o 100 Amps EHTL1_A
Elec. Heat Amps Leg 2 0 t o 100 Amps EHTL2_A
Elec. Heat Amps Leg 3 0 t o 100 Amps EHTL3_A
Gas Supply Type 0=Natural,
1=LP
GASTYPE
GAS INLET PRESSURE 0to20 IN_HG_OF_KPAG GASPRESS
STAGE 1 GAS PRESSURE 0to20 IN_HG_OF_KPAG HT1PRESS
STAGE 2 GAS PRESSURE 0to20 IN_HG_OF_KPAG HT2PRESS