141
APPENDIX D: SystemVut Controller CCN Tables
Setpoint Table
Tab le N am e Display Name Range Units Point Name Default
SET_PNT
Occupied Cool Setpoint 55 to 80 °F OCSP 78
Occupied Heat Setpoint 55 to 80 °F OHSP 68
Unoccupied Cool Setpoint 65 t o 95 °F UCSP 85
Unoccupied Heat Setpoint 40 to 80 °F UHSP 60
Heat---Cool Setpoint Gap 2to10 ^F HCSP_GAP 5
SPT Offset Range (+/--- ) 0to5 °F SPTO_RNG 5
Occupied SPRH Setpoint 0 to 100 % SPRH_OSP 55
Unoccupied SPRH Setpoint 0 to 100 % SPRH_USP 55
Control ID Table
Tab le N am e Display Name Range Units Point Name Default
CTLRID
Device Name: 48_50LC_
Description: text string
Location: text string
Software Part Number: CES R131651---XX--- XX
Model Number: 2to10
Serial Number: 0to5
Reference Number: 0to5