Table 35 – LC 07--26 VFD Parameters Configured by Factory or VFD Keypad
Parameter Group Parameter Title Danfoss Parameter VFD Default CARRIER
Reset Functions Service Code 14--- 29 6333 6222
FC Port Settings
PROTOCOL 8 --- 3 0 (0) FC (20) LEN
ADDRESS 8 --- 3 1 1 180
BAUD RATE 8 --- 3 2 (2) 9.6 kb/s (4) 38.4 kb/s
Parity/Stop Bits 8 --- 3 3 (0) 8 EVEN 1 (2) 8 NONE 1
Table 36 – LC 07--26 VFD Parameters Hard Coded by SystemVut Controller
Parameter Group Parameter Title Danfoss Parameter VFD Default CARRIER
Basic Settings Regional Settings 0 --- 0 3 International (0) North America (1)
General Settings
Configuration Mode 1 --- 0 0 Open Loop (0) Open Loop (0)
Torque Characteristics 1 --- 0 3 Variable Torque (1) Variable Torque (1)
Clockwise Direction 1 --- 0 6 Normal (0) Normal (0)
Motor Selection Motor Construction 1 --- 1 0 Asynchron (0) Asynchron (0)
Start Adjustments
Start Delay 1 --- 7 1 0s 0s
Start Function 1 --- 7 2 Coast/delay time (2) Coast/delay time (2)
Flying Start 1 --- 7 3 Disabled (0) Disabled (0)
Motor Temperature Motor Thermal Protection 1 --- 9 0 No Protection (0) ETR trip 1 (4)
Brake Energy Funct. Over--- voltage Control 2 --- 1 7 Enabled (2) Enabled (2)
References
Preset Reference 3 --- 1 0 %00005 %00005
Reference 3 Source 3 --- 1 7 Local bus reference (11) Local bus reference (11)
Motor Limits
Motor Speed Direction 4 --- 1 0 Both directions (2) Both directions (2)
Motor Speed Low Limit [H z] 4 --- 1 2 0hz 0hz
Motor Speed High Limit [Hz] 4 --- 1 4 65hz 65hz
Digital Inputs
Terminal 18 Digital Input 5 --- 1 0 8 Start (8)
Terminal 27 Digital Input 5 --- 1 2 Coast Inverse (2) No Operation (0)
Relays
Function Relay (Relay 1) 5 --- 4 0 No Function (0) Bus Control (45)
Function Relay (Relay 2) 5 --- 4 0 No Function (0) Bus Control (45)
Analog/Digital Output
Te r mi n a l 4 5 M o d e 6 --- 7 0 0 --- 2 0 m A ( 0 ) 4 --- 2 0 m A ( 1 )
Terminal 45 Analog Output 6 --- 7 1 No Operation (0) Bus Control (139)
Te r mi n a l 4 5 O u t p ut M in Sc a l e 6 --- 7 3 %00005 %00005
Analog/Digital Output
Te r mi n a l 4 2 M o d e 6 --- 9 0 0 --- 2 0 m A ( 0 ) 0 --- 2 0 m A ( 0 )
Terminal 42 Analog Output 6 --- 9 1 No Operation (0) Bus Control (139)
Te r mi n a l 4 2 O u t p ut M in Sc a l e 6 --- 9 3 %00005 %00005
General Settings
Control Site 8 --- 0 1 Digital and ctrl.word (0) Digital and ctrl.word (0)
Control Source 8 --- 0 2 FC Port (1) FC Port (1)
Control Timeout Function 8 --- 0 4 Off (0) Stopandtrip(5)
Digital/Bus Start Select 8 --- 5 3 Logic OR (3) Logic AND (2)
SLC Settings SL Controller Mode 13--- 00 Off (0) Off (0)
Inverter Switching Switching Frequency 14--- 01 5.0khz (5) 5.0khz (5)
Mains On/Off Function at Mains Imbalance 14--- 12 Tri p ( 0 ) Trip (0)
Reset Functions Reset Mode 14--- 20 Manual Reset (0) Automatic reset x 3 (3)
Table 37 – LC 07 --26 VFD Parameters Configurable Through SystemVu Controller
Parameter
Group
Parameter Title
Danfoss
Parameter
HVAC Default CARRIER CCN Point Display Menu Item
Motor Data
Motor Power 1 --- 2 0 drive dep. See Table 39 or 40 MOTPHP IDF VFD NOM HP
Motor Voltage 1 --- 2 2 drive dep. S ee Table 39 or 40 MOTVOL T IDF VFD VOLTAGE
Motor Frequency 1 --- 2 3 50hz 60hz MOTFREQ IDF VFD NOM. FREQ
Motor Current 1 --- 2 4 drive dep. See Table 39 or 40 MOTCUR IDF VFD NOM. AMPS
Motor Nominal Speed 1 --- 2 5 drive dep. S ee Table 39 or 40 MOTNOMSP IDF VFD NOM. RPM
Reference Limits
Minimum Reference 3 --- 0 2 0hz 0h z MINREF IDF VFD MIN REF
Maximum Reference 3 --- 0 3 50hz 60hz MAXREF IDF VFD MAX REF
Ramp 1
Ramp1RampUpTime 3 --- 4 1 3s 10s RAMPUP_T VFD ACCEL. TIME
Ramp 1 Ramp Down Time 3 --- 4 2 3s 30s RAMPDN_T VFD DECEL. TIME
Motor Limits Current Limit 4 --- 1 8 110% 100% CURRLMT IDF VFD AMP LIMIT
General Settings Control Timeout Time 8 --- 0 3 1s 30s CNT_TOUT IDF VFD TIMEOUT
Reset Functions Automatic Restart Time 14--- 21 10s 30s ARSTRT_T IDF VFD RESET DUR
Environment RF I Filter 14--- 50 On (1) On (1) RFIFILTR VFD RFI FILTER