80
APPENDIX A: SystemVut Controller Display
Settings Main Menu Layout (cont)
Display Text Expanded Text Range Units Default Point
UNIT CONFIGURATIONS (cont) Unit Configurations Menu
SWITCH INPUTS CONFIGS DI Config Menu
FIRE SHUTDOWN SW Fire Shutdown Switch 0=NORM OPEN,
1=NORM CLSD,
2=NO SWITCH
2: no FIOP
0: FIOP
FIRE_CFG
HUMSTAT CHANNEL HumidistatStatus Channel 0=None,
1=MBB DI12,
2=MBB DI13.
3=MBB DI14,
4=MBB DI02,
5=MBB DI04,
6=SIOB Di01
0=for all except
Humidimizer
6=Humidimizer Units
HUMDCHAN
HUMSTAT SW TYPE Humidistat Switch Type 0=NORM OPEN,
1=NORM CLSD,
0=NORM OPEN HUMD_CFG
FILTER SW CHANNEL Filter Status Sw Channel 0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04
0=None FILTCHAN
FILTER SW TYPE Filter Status Swith Type 0=NORM OPEN,
1=NORM CLSD
0=NORM OPEN FILT_CFG
REMOTE OCC CHAN Remote Occupancy Channel 0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04
0=None RMOCCHAN
REMOTE OCC TYPE Remote Occupancy Sw Type 0=NORM OPEN,
1=NORM CLSD
0=NORM OPEN RMOC_CFG
REM.SHUTDOWN CH AN Remote Shutdown Channel 0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04
0=None ROFFCHAN
REM.SHUTDOWN SW T Remote Shutdown Sw Type 0=NORM OPEN,
1=NORM CLSD
0=NORM OPEN ROFF_CFG
REM.SHUTDOWN TYPE Remote Shutdown ALM Type 0=Normal,
1=Emergency
0=Normal ROFFTYPE
COFS CHANNEL COFS Assigned Channel 0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04
0=None COFSCHAN
COFS TYPE COFS Switch Type 0=NORM OPEN,
1=NORM CLSD
1=NORM CLSD COFS_CFG
GEN STATUS CHAN General Status Channel 0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04
0=None GEN_CHAN
GEN STAT SW TYPE General Status Sw Type 0=NORM OPEN,
1=NORM CLSD
0=NORM OPEN GENS_CFG
SHUTDOWN GEN STAT General Status shutdown? Yes/No Yes GENFATAL
ENTHALPY SW CHAN Enthalpy Sw Channel 0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04
0=None ENTHCHAN
ENTHALPY SW TYPE Enthalpy Switch Type 0=NORM OPEN,
1=NORM CLSD
0=NORM OPEN EN TH_CFG
ANALOG INPUT CONFIGS Analog Inputs Configuration Menu
SPRH SENS CHANNEL SPRH Assigned Channel 0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08
4=SIOB AI10
0=None SPRHCHAN
SPRH RH @ 4MA SPRH Sensor Value at 4mA 0 to 100 % 0 SPRH_4MA
SPRH RH @ 20MA SPRH Sensor V alue @ 20mA 0 to 100 % 1 SPRH20MA
IAQ SENSOR CHAN IAQ Assigned Channel 0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08
0: no FIOP
1: FIOP
IAQ_CHAN
IAQ PPM @ 4MA IAQ Sensor Value at 4mA 0 to 5000 ppm 0 IAQ_4MA
IAQ PPM @ 20MA IAQ Sensor Value at 20mA 0 to 5000 ppm 2000 IAQ_20MA