EasyManua.ls Logo

Carrier 48NHT024 - Cooling Section Startup and Adjustments

Carrier 48NHT024
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
blower
motor.
Check
blower
wheel
for
correct
rotation
as
indicated
by
arrow
on
blower
housing.
If
blower
wheel
rotates
in
opposite
direction,
reverse
any
two
blower
motor
leads
or
any
two
line
voltage
leads.
Recheck
blower
wheel
rotation
if
necessary
to
reverse
leads.
B.
Checking
and
Adjusting
Refrigerant
Charge
The
refrigerant
system
is
fully
charged
with
R-22
refriger¬
ant,
tested,
and
factory-sealed.
NOTE:
Adjustment
of
the
refrigerant
charge
is
not
required
unless
the
unit
is
suspected
of
not
having
the
proper
R-22
charge.
For
all
applications,
the
correct
R-22
charge
for
the
best
performance
is
the
charge
that
results
in
a
suction
gas
superheat
of
5
F
at
the
compressor
inlet
when
the
unit
is
operating
at
the
ARI
rating
conditions
of
95
F
DB
outdoor
and
80
F
DB/67
F
WB
indoor.
A
superheat
charging
label
is
attached
to
the
outside
of
the
compressor
access
door.
The
label
includes
a
“Field
Super¬
heat
Charging
Table”
and
a
“Required
Suction-Tube
(F)”
temperature
chart.
An
accurate
superheat
thermocouple-,
or
thermistor-type
thermometer,
a
sling
psychrometer,
and
a
gauge
manifold
are
required
when
using
the
superheat
charging
method
for
evaluating
the
unit
charge.
Do
not
use
mercury
or
small
dial-type
thermometers
because
they
are
not
adequate
for
this
type
of
measurement.
A
CAUTION
When
evaluating
the
refrigerant
charge,
an
indicated
adjustment
to
the
specified
factory
charge
must
always
be
very
minimal.
If
a
substantial
adjustment
is
indi¬
cated,
an
abnormal
condition
exists
somewhere
in
the
cooling
system;
such
as
insufficient
airflow
across
either
coil
or
both
coils.
Proceed
as
follows:
1.
Remove
caps
from
low-
and
high-pressure
service
fittings.
2.
Using
hoses
with
valve
core
depressors,
attach
low-and
high-pressure
gauge
hoses
to
low-
and
high-pressure
service
fittings,
respectively.
3.
Start
unit
in
cooling
mode
and
let
unit
run
until
system
pressures
stabilize.
4.
Measure
and
record
the
following:
a.
Outdoor
ambient-air
temperature
(F
DB).
b.
Evaporator
inlet-air
temperature
(F
WB).
c.
Suction-tube
temperature
(F)
at
low-side
service
fit¬
ting.
d.
Suction
(low-side)
pressure
(PSIG).
5.
Using
“Field
Superheat
Charging
Table,"
compare
PILOT
FLAME
BURNER
FLAME
outdoor-air
temperature
(F
DB)
with
evaporator
inlet-
air
temperature
(F
WB)
to
determine
desired
system
operating
superheat
temperature.
See
Table
10.
6.
Next,
using
“Required
Suction-Tube
(F)”
table,
com¬
pare
desired
superheat
temperature
with
suction
(low-
side)
operating
pressure
(PSIG)
to
determine
proper
suction-tube
temperature.
See
Table
11.
7.
Compare
actual
suction-tube
temperature
with
proper
suction-tube
temperature.
Using
a
tolerance
of
3
F,
add
refrigerant
if
actual
temperature
is
more
than
3
F
higher
than
proper
suction-tube
temperature,
or
remove
refrigerant
if
actual
temperature
is
more
than
3
F
lower
than
required
suction-tube
temperature.
NOTE:
If
the
problem
causing
the
inaccurate
readings
is
a
refrigerant
leak,
see
Step
7,
part
B,
of
these
instructions.
C.
Indoor
Airflow
and
Airflow
Adjustments
A
CAUTION
For
cooling
operation,
the
recommended
airflow
is
350
to
450
Cfm
per
each
12,000
Btuh
of
rated
cooling
capac¬
ity.
For
heating
operation,
the
airflow
must
produce
a
temperature
rise
that
falls
within
the
range
stamped
on
the
unit
rating
plate.
Model
018-048
size
units
have
direct-drive
blower
motors.
Blower
motors
are
factory-connected
to
deliver
the
proper
heating
and
cooling
airflows
at
normal
external
static
pres¬
sures
(medium
speed
cooling,
low
speed
heating
for
230v
units
and
high
speed
cooling,
heating
for
460v
units).
060
size
units
have
belt
drive
blower
motors
which
have
the
motor
pulley
factory
set
at
four
turns
open.
For
208v
operation
on
208/230v
rated
direct
drive
units,
interchange
motor
leads
to
high
speed
for
cooling
and
medium
speed
for
heating
operation.
Table
9
shows
the
temperature
rise
at
various
airflow
rates.
Tables
12
and
13
show
both
heating
and
cooling
airflows
at
various
external
static
pressures.
Refer
to
these
tables
to
determine
the
airflow
for
the
system
being
installed.
See
Tables
2
thru
7
for
the
rated
heating
and
cooling
airflows.
NOTE:
Be
sure
that
all
supply-
and
return-air
grilles
are
open,
free
from
obstructions,
and
adjusted
properly.
A
WARNING
Disconnect
electrical
power
to
the
unit
before
changing
blower
speed.
(Be
sure
to
turn
off
gas
supply
before
dis¬
connecting
electrical
power.)
Electrical
shock
can
cause
personal
injury
or
death.
13

Related product manuals