EasyManua.ls Logo

Carrier 48NHT024 - Gas Piping Installation

Carrier 48NHT024
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table
1—Maximum
Gas
Flow
Capacity
of
Pipe
in
Cubic
Feet
of
Gas
Per
Hour
for
Gas
Pressures
of
0.5
PSIG
or
Less
and
a
Pressure
Drop
of
0.5
Inch
Water
Column
(Based
on
a
0.60
Specific
Gravity
Gas)
Nominal
Iron
Pipe,
Size,
Inches
Internal
Diameter,
Inches
Length
of
Pipe,
Feet*
10
20
30
40
50
60
70
80
90
100
125
150
175
200
1/2
.622
175
120
97
82
73
66
61
57
53
50
44
40
3/4
.824
360
250
200
170
151
138
125
118
110
103
93
84
77
72
1
1.049
680
465
375
320
285
260
240
220
205
195
175
160
145
135
1-1/4
1.380
1,400
950
770
600
580
530
490
460
430
400
360
325
300
280
1-1/2
1.610
2,100
1,460
1,180
990
900
810
750
690
650
620
550
500
460
430
Ref:
Table
C-4,
NFPA
54—1984
This
length
includes
an
ordinary
number
of
fittings.
A
CAUTION
The
venting
system
is
designed
to
ensure
proper
vent¬
ing.
The
vent
cap
assembly
must
be
installed
as
indi¬
cated
in
this
section
of
the
unit
Installation
Instructions.
NOTE:
Screw
holes
in
the
flue
assembly
and
the
unit
flue
panel
are
not
symmetrically
located;
thereby,
ensuring
proper
orientation
when
installing
these
components.
Refer
to
Fig.
6
and
install
the
vent
cap
as
follows:
1.
Place
vent
cap
assembly
over
flue
panel,
orient
screw
holes
in
vent
cap
with
holes
in
flue
panel,
and
secure
vent
cap
in
place
by
inserting
the
single
screw
on
the
right
side
of
vent
cap.
2.
Place
the
vent
cap
guard
over
the
vent
cap,
orient
holes
in
vent
cap
guard
with
holes
in
vent
cap
and
flue
panel.
Secure
the
entire
assembly
with
the
remaining
two
screws
on
the
left
side
of
vent
cap
and
vent
cap
guard
assembly.
Step
4—Gas
Piping
The
gas
supply
pipe
enters
the
unit
through
the
access
hole
provided.
The
gas
connection
to
the
unit
is
made
to
the
1/2-in.
FPT
gas
inlet
on
the
manual
shutoff
or
gas
valve.
Install
a
separate
gas
supply
line
that
runs
directly
from
the
meter
to
the
heating
section.
Refer
to
Table
1
and
the
National
Fuel
Gas
Code
for
gas
pipe
sizing.
Do
not
use
cast-
iron
pipe.
Check
the
local
utility
for
recommendations
con¬
cerning
existing
lines.
Choose
a
supply
pipe
that
is
large
enough
to
keep
the
pressure
loss
as
low
as
practical.
Never
use
pipe
smaller
than
the
1/2-in.
FPT
gas
inlet
on
the
unit
gas
valve.
When
installing
the
gas
supply
line,
observe
local
codes
per¬
taining
to
gas
pipe
installations.
Refer
to
the
National
Fuel
Gas
Code
ANSI
Z223.1-1984
(In
Canada,
CAN/CGA
B
149.1,
(2)-M86)
or
NFPA
54-1984
in
the
absence
of
local
building
codes.
Adhere
to
the
following
pertinent
recom¬
mendations:
1.
Avoid
low
spots
in
long
runs
of
pipe.
Grade
all
pipe
1/4-in.
in
every
15-ft
to
prevent
traps.
Grade
all
hori¬
zontal
runs
downward
to
risers.
Use
risers
to
connect
to
heating
section
and
to
meter.
2.
Protect
all
segments
of
piping
system
against
physical
and
thermal
damage.
Support
all
piping
with
appropri¬
ate
straps,
hangers,
etc.
Use
a
minimum
of
one
hanger
every
6-ft.
For
pipe
sizes
larger
than
1/2-in.,
follow
rec¬
ommendations
of
national
codes.
3.
Apply
joint
compound
(pipe
dope)
sparingly
and
only
to
male
threads
of
joint
when
making
pipe
connections.
Use
only
pipe
dope
that
is
resistant
to
action
of
lique¬
fied
petroleum
gases
as
specified
by
local
and/or
national
codes.
Never
use
teflon
tape.
4.
Install
sediment
trap
in
riser
leading
to
heating
sec¬
tion.
This
drip
leg
functions
as
a
trap
for
dirt
and
con¬
densate.
Install
trap
where
condensate
can
not
freeze.
Install
this
sediment
trap
by
connecting
a
piping
tee
to
riser
leading
to
heating
section,
so
that
straight-
through
section
of
tee
is
vertical.
See
Fig.
7.
Then,
con¬
nect
capped
nipple
into
lower
end
of
tee.
Extend
capped
nipple
below
level
of
gas
controls.
5.
Install
an
accessible,
external,
manual
main
shut-off
valve
in
gas
supply
pipe
within
6-ft
of
heating
section.
6.
Install
ground-joint
union
close
to
heating
section
between
unit
manual
shutoff
and
external
manual
main
shut-off
valve.
7.
Pressure-test
all
gas
piping
in
accordance
with
local
and
national
plumbing
and
gas
codes
before
connecting
piping
to
unit.
NOTE:
When
pressure
testing
the
gas
supply
system
after
the
gas
supply
piping
has
been
connected
to
the
unit
gas
valve,
the
supply
piping
must
be
disconnected
from
the
gas
valve
during
any
pressure
testing
of
the
piping
systems
at
test
pressure
in
excess
of
0.5
psig.
When
pressure
testing
the
gas
supply
piping
system
at
test
pressures
equal
to
or
less
than
0.5
psig,
the
unit
heating
section
must
be
isolated
from
the
gas
piping
system
by
closing
the
external
main
manual
shut-off
valve
and
slightly
opening
the
ground-joint
union.
Fig.
6—Vent
Cap
Assembly
5

Related product manuals