A
CAUTION
Unstable
operation
may
occur
when
the
gas
valve
and
manifold
assembly
are
forced
out
of
position
while
con¬
necting
improperly
routed
rigid
gas
piping
to
the
gas
valve.
Use
a
backup
wrench
when
making
connection
to
avoid
strain
on,
or
distortion
of,
the
gas
control
piping.
A
CAUTION
If
a
flexible
conductor
is
required
or
allowed
by
the
authority
having
jurisdiction,
black
iron
pipe
shall
be
installed
at
the
gas
valve
and
extend
a
minimum
of
2-ins.
outside
the
unit
casing.
A
WARNING
Never
use
a
match
or
other
open
flame
when
checking
for
gas
leaks.
Never
purge
gas
line
into
combustion
chamber.
Failure
to
adhere
to
this
warning
could
result
in
an
explosion.
8.
Check
for
gas
leaks
at
all
field-installed
and
factory-
installed
gas
lines
after
all
piping
connections
have
been
completed.
Use
soap-and-water
solution
(or
method
specified
by
local
codes
and/or
regulations).
Step
5—Duct
Connections
Model
48N
has
duct
flanges
on
the
supply-
and
return-air
openings
on
the
side
and
bottom
of
the
unit.
See
Figs.
2
and
3
for
connection
sizes
and
locations.
NOTE:
The
design
and
installation
of
the
duct
system
must
be
in
accordance
with
the
standards
of
the
National
Fire
Protection
Association
for
installation
of
nonresidence-type
air
conditioning
and
ventilating
systems,
NFPA
No.
90A
or
residence-type,
NFPA
No.
90B;
and/or
local
codes
and
ordinances.
Adhere
to
the
following
criteria
when
selecting,
sizing,
and
installing
the
duct
system:
1.
R
emove
appropriate
panels
from
unit
to
obtain
either
side
or
bottom
discharge.
If
models
48NLT018
thru
48NMT042
are
installed
in
horizontal
discharge
appli¬
cations,
remove
side
duct
covers,
save
screws,
and
install
the
covers
on
bottom
duct
openings.
For
models
48NHT036
thru
48NHT060
remove
either
side
or
bot¬
tom
duct
covers
as
needed
and
discard.
2.
S
elect
and
size
ductwork,
supply-air
registers,
and
return-air
grilles
according
to
ASHRAE
recom¬
mendations.
A
CAUTION
When
the
duct-system
fastening
holes
are
being
drilled
into
side
of
Model
48N
instead
of
the
unit
duct
flanges,
use
extreme
care
to
avoid
puncturing
the
coil
or
coil
tubes.
3.
Use
flexible
transition
between
rigid
ductwork
and
unit
to
prevent
transmission
of
vibration.
The
transition
may
be
screwed
or
bolted
to
duct
flanges.
Use
suitable
gaskets
to
ensure
weather
and
airtight
seal.
4.
Install
external,
field-supplied
air
filter(s)
in
return-air
ductwork
where
it
is
easily
accessible
for
service.
Rec¬
ommended
filter
sizes
are
shown
in
Tables
2
thru
7.
5.
Size
all
ductwork
for
maximum
required
airflow
(either
heating
or
cooling)
for
unit
being
installed.
Avoid
abrupt
duct
size
increases
or
decreases.
6.
Adequately
insulate
and
weatherproof
all
ductwork
located
outdoors.
Insulate
ducts
passing
thru
uncondi¬
tioned
space,
and
use
vapor
barrier
in
accordance
with
latest
issue
of
SMACNA
and
ACC
A
minimum
installa¬
tion
standards
for
heating
and
air
conditioning
sys¬
tems.
Secure
all
ducts
to
building
structure.
7.
Flash,
weatherproof,
and
vibration-isolate
all
openings
in
building
structure
in
accordance
with
local
codes
and
good
building
practices.
Step
6—Electrical
Connections
1.
Make
all
electrical
connections
in
accordance
with
National
Electrical
Code
ANSI/NFPA
70-1987
and
local
electrical
codes
governing
such
wiring.
In
Canada,
all
electrical
connections
must
be
in
accordance
with
CSA
standard
C22.1
Canadian
Electrical
Code
Part
1
and
applicable
local
codes.
Refer
to
Unit
Wiring
Diagram.
2.
Use
only
copper
conductor
for
connections
between
field-supplied
electrical
disconnect
switch
and
unit.
DO
NOT
USE
ALUMINUM
WIRE.
3.
Ensure
that
high-voltage
power
to
unit
is
within
oper¬
ating
voltage
range
indicated
on
unit
rating
plate.
On
3-phase
units,
ensure
that
phases
are
balanced
within
2%.
Consult
local
power
company
for
correction
of
improper
voltage
and/or
phase
balance.
6