Bhp
Table 30 -- Fan Performance -- 48PGF/N07 Horizontal Units
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Of m)
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
AIRFLOW
(Cfm)
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
LEGEND
-- B_ke Horsepower
Rpm
651
683
715
748
781
815
850
885
920
956
992
1028
1064
0.2
Bhp
0.40
0.47
0.54
0.62
0.71
0.81
0.92
1.04
1.17
1.31
1.46
1.62
1.80
Rpm
739
767
796
826
856
888
919
952
985
1018
1052
1086
1121
0.4
Bhp
0.51
0.58
0.66
0.75
0.84
0.95
1.06
1.18
1.32
1.47
1.62
1.79
1.98
0.6
Bpm Bhp
817 0.62
843 0.69
869 0.78
896 0.87
925 0.97
954 1.08
983 1.20
1014 1.33
1045 1.47
1076 1.63
1108 1.79
1141 1.96
1174 2.15
Rpm
889
912
937
962
988
1015
1043
1072
1101
1131
1162
1193
1225
0.8
Bhp
0.73
0.81
0.90
1.O0
1.10
1.22
1.35
1.48
1.63
1.79
1.96
2.14
2.33
Rpm
957
978
1000
1024
1048
1074
1100
1127
1155
1184
1213
1243
1.0
Bhp
0.85
0.93
1.03
1.13
1.24
1.36
1.49
1.63
1.79
1.95
2.12
2.31
Rpm
1022
1041
1061
1083
1106
1130
1155
1180
1207
1234
1262
1.2
Bhp
0.97
1.06
1.16
1.26
1.38
1.51
1.64
1.79
1.95
2.11
2.29
Rpm
1083
1101
1119
1140
1161
1183
1207
1231
1257
1283
AVAILABLE EXTERNAL STATIC PRESSURE (in. w_l!
1.4
Bhp
1.10
1.19
1.29
1.40
1.52
1.65
1.80
1.95
2.11
2.28
1.6
Rpm Bhp
1143 1.23
1159 1.32
1176 1.43
1194 1.55
1214 1.67
1236 1.81
1258 1.95
1281 2.11
1305 2.27
Rpm
1201
1215
1230
1248
1266
1286
1307
1329
1.8
Bhp
1.36
1.46
1.57
1.69
1.82
1.96
2.11
2.27
Rpm
1256
1269
1283
1299
1317
1335
1355
2.0
Bhp
1.50
1.60
1.72
1.84
1.98
2.12
2.27
NOTES:
1. Motor drive range is 796 to 1128 rpm for low range motor/drive and 1150 to
1438 rpm for high range motor/drive. All other rpms require a field-supplied
drive,
2. Maximum continuous bhp is 2.40 for low range motor/drive and 3.10 for high
range motor/drive.
3. See below for General Fan Performance Notes.
GENERAL NOTES FOR FAN PERFORMANCE DATA TABLES
1. Static pressure losses (i.e., economizer, etc.) must be added to
external static pressure before entering Fan Performance table.
2. Interpolation is permissible. Do not extrapolate.
3. Fan performance is based on wet coils, clean filters, and casing
losses. Refer to the unit Product Data literature for Accessory/
FlOP Static Pressure information.
4. Extensive motor and drive testing on these units ensures that
the full horsepower range of the motor can be utilized with
confidence. Using the fan motors up to the bhp rating shown
will not result in nuisance tripping or premature motor failure.
Unit warranty will not be affected.
5. Use of a field-supplied motor may affect wire size. Recalculate
the unit power supply MCA and MOCP if required. Contact the
local Carrier representative for details.
6. Use the following formula to calculate input watts:
Input Watts = Bhp x (746/Motor Eft)
Table 31 -- Operation Air Quantity Limits
UNIT
48PG
03
04 (Low Heat)
04 (Med Heat)
04 (High Heat)
05 (Low Heat)
05 (Med Heat)
05 (High Heat)
06 (Low Heat)
06 (Med Heat)
06 (High Heat)
07 (Low Heat)
07 (Med Heat)
07 (High Heat)
COOLING (cfm) HEATING (cfm)
Min Max Min Max
600 1000 600 1680
900 1500 600 1680
900 1500 940 2810
900 1500 1130 2820
1200 2000 600 1680
1200 2000 940 2810
1200 2000 1130 2820
1500 2500 940 2810
1500 2500 1130 2820
1500 2500 1510 2520
1800 3000 940 2810
1800 3000 1130 2820
1800 3000 1510 2520