Table 32 -- Evaporator Fan Motor Specifications
48PG DRIVE VOLTAGE/PHASE MOTOR P/N EFFICIENCY MAX BHP MAX AMPS
Low 208/lph HC52EE208 0.73 0.85 4.0
03 230/lph HC52EE208 0.73 0.85 4.0
208/lph HC52EE208 0.73 0.85 4.0
High 230/lph HC52EE208 0.73 0.85 4.0
208/lph HC52EE208 0.73 0.85 4.0
230/lph HC52EE208 0.73 0.85 4.0
Low 208/3ph HC52EE208 0.73 0.85 4.0
230/3ph HC52EE208 0.73 0.85 4.0
460/3ph HC52EE460 0.73 0.85 2.0
04 575/3ph HC52EE576 0.73 0.85 1.6
208/lph HC52EE208 0.73 0.85 4.0
230/lph HC52EE208 0.73 0.85 4.0
208/3ph HC52EE208 0.73 0.85 4.0
High 230/3ph HC52EE208 0.73 0.85 4.0
460/3ph HC52EE460 0.73 0.85 2.0
575/3ph HC52EE576 0.73 0.85 1.6
208/lph HC52EE208 0.73 0.85 4.0
230/lph HC52EE208 0.73 0.85 4.0
Low 208/3ph HC52EE208 0.73 0.85 4.0
230/3ph HC52EE208 0.73 0.85 4.0
460/3ph HC52EE460 0.73 0.85 2.0
05 575/3ph HC52EE576 0.73 0.85 1.6
208/lph HC54FB230 0.78 1.6 8.3
230/lph HC54FB230 0.78 1.6 8.3
208/3ph HD56FE652 0.80 2.4 6.4
High 230/3ph HD56FE652 0.80 2.4 6.4
460/3ph HD56FE652 0.80 2.4 3.2
575/3ph HD56FE575 0.80 2.4 2.4
208/lph HC52EE208 0.73 0.85 4.0
230/lph HC52EE208 0.73 0.85 4.0
Low 208/3ph HD56FE652 0.80 2.4 6.4
230/3ph HD56FE652 0.80 2.4 6.4
460/3ph HD56FE652 0.80 2.4 3.2
06 575/3ph HD56FE575 0.80 2.4 2.4
208/lph HC54FB230 0.78 1.6 8.3
230/lph HC54FB230 0.78 1.6 8.3
208/3ph HD56FE652 0.80 2.4 6.4
High 230/3ph HD56FE652 0.80 2.4 6.4
460/3ph HD56FE652 0.80 2.4 3.2
575/3ph HD56FE575 0.80 2.4 2.4
208/3ph HD56FE652 0.80 2.4 6.4
Low 230/3ph HD56FE652 0.80 2.4 6.4
460/3ph HD56FE652 0.80 2.4 3.2
07 575/3ph HD56FE575 0.80 2.4 2.4
208/3ph HD58FE653 0.84 3.1 8.8
230/3ph HD58FE653 0.84 3.1 8.8
High 460/3ph HD58FE653 0.84 3.1 4.4
575/3ph HD58FE576 0.82 3.7 4.2
NOTES:
1. Extensive motor and electrical testing ensures that the motors can be
utilized with confidence up to the maximum applied bhp, watts, and
amps. Using the fan motor up to the maximum ratings shown will not
result in nuisance tripping or premature motor failure. Unit warranty will
not be affected.
2. Convert bhp to watts using the following formula:
watts = bhp (746)
motor efficiency
3. The EPACT (Energy Policy Act of 1992) regulates energy requirements
for specific types of indoor fan motors. Motors regulated by EPACT
include any general purpose, T-frame (three-digit, 143 and larger),
single-speed, foot mounted, polyphase, squirrel cage induction motors of
NEMA (National Electrical Manufacturers Association) design A and B,
manufactured for use in the United States. Ranging from 1 to 200 Hp,
these continuous-duty motors operate on 230 and 460 volt, 60 Hz power.
If a motor does not fit into these specifications, the motor does not have
to be replaced by an EPACT-compliant energy-efficient motor. Variable-
speed motors are exempt from EPACT compliance requirements. There-
fore, the indoor fan motors for Carrier 48PG03-07 units are exempt from
these requirements.
Table 33 -- Fan Rpm at Motor Pulley Settings*
UNIT
48PG
03
04
05
06
07
DRIVE
0
Low 736
High 1001
Low 736
High 1128
Low 910
High 1173
Low 978
High 1261
Low 1128
High 1438
MOTOR PULLEY TURNS OPEN
l& 1 1l& 2 2l& 3 316 4 416 5
710 685 660 634 609 583 558 533 507 482
966 932 897 863 828 794 759 725 690 656
710 685 680 634 609 583 558 533 507 482
1095 1062 1028 995 962 929 896 863 829 796
878 847 815 784 753 721 690 659 627 596
1139 1104 1070 1035 1001 966 932 897 883 828
949 920 891 863 834 805 776 748 719 690
1227 1194 1161 1128 1095 1062 1028 995 962 929
1095 1062 1028 995 962 929 896 863 829 796
1409 1380 1351 1323 1294 1265 1236 1208 1179 1150
*Approximate fan rpm shown, based on 1725 rpm motor.