100
APPENDIX A — LOCAL DISPLAY AND CCN TABLES (cont)
MODE — CONFIGURATION (cont)
LEGEND
FIOP — Factory-Installed Option
ITEM EXPANSION RANGE UNITS DEFAULT CCN TABLE/SUB-TABLE CCN POINT PAGE NO.
CONFIGURATION (cont)
AIR.Q Air Quality Configuration IAQ_CFG
IA.CF IAQ Analog Input Config 0=No IAQ
1=Demand Ventilation
2=Econ Position Override
3=Econ Min Position Control
0: no FIOP
1: FIOP
IAQANCFG 39, 49, 82
IA.FN IAQ Analog Fan Config 0=Never
1=Only While Occupied
2=Always
0 IAQANFAN 41, 51
II.CF IAQ Switch Input Config 0=No IAQ
1=DCV Normally Open
2=DCV Normally Closed
3=Override Normally Open
4=Override Normally Closed
0 IAQINCFG 39, 49, 50
II.FN IAQ Switch Fan Config 0=Never
1=Only While Occupied
2=Always
0 IAQINFAN 41
AQ.MN Econo Min IAQ Position 0 to 100 10 IAQMINP 49
EC.MN Econo Minimum Position 0 to 100 30 ECONOMIN 49, 50
OVR.P IAQ Override Position 0 to 100 100 IAQOVPOS 49, 50
OA.CF OAQ Analog Input Cfg 0=No OAQ
1=Demand Ventilation
2=Outdoor Air Lockout
0 OAQANCFG 39, 49, 50,
82
OAQ.L OAQ Lockout Limit 0 to 5000 600 OAQLOCK 50
AQD.L AQ Differential Low 0 to 5000 100 DAQ_LOW 49
AQD.H AQ Differential High 0 to 5000 700 DAQ_HIGH 49
DF.ON Fan On AQ Differential 0 to 5000 600 DAQFNON 50
DF.OF Fan Off AQ Differential 0 to 5000 200 DAQFNOFF 50
I.4M IAQ Sensor Value at 4mA 0 to 5000 0 IAQ_4MA 49
I.20M IAQ Sensor Value at 20mA 0 to 5000 2000 IAQ_20MA 49
O.4M OAQ Sensor Value at 4mA 0 to 5000 0 OAQ_4MA 50
O.20M OAQ Sensor Value at 20mA 0 to 5000 2000 OAQ_20MA 50
H.4M RH Sensor Value at 4mA 0 to 50 % 0 RH_4MA 47
H.20M RH Sensor Value at 20mA 60 to 100 % 100 RH_20MA 47
ALM.O Alarm Relay Configuration ALM_CFG 52
A.SPC SPT/SPRH Sensor Failure Yes/No Yes SPACE_AL
A.SRT SAT/RAT Sensor Failure Yes/No Yes SATRATAL
A.OAT OAT Thermistor Failure Yes/No Yes OAT_AL
A.CS Current Sensor Failure Yes/No Yes CS_AL
A.CMP Compressor Failure Yes/No Yes COMP_AL
A.CKT Refrigerant Circuit Failure Yes/No Yes CKT_AL
A.SSP SSP Transducer Failure Yes/No Yes SSP_AL
A.SCT SCT Thermistor Failure Yes/No Yes SCT_AL
A.FAN Indoor Fan Failure Yes/No Yes FAN_AL
A.FIL Dirty Filter Yes/No Yes FILT_AL
A.TST Thermostat Failure Yes/No Yes TSTAT_AL
A.ECO Economizer Failure Yes/No Yes ECON_AL
TRIM Sensor Calibration (CCN TRIM — see
Maintenance Display) 64
SPT.C Space Temp Calibration –30 to 120 dF 64
SPT.T Space Temp Trim –30 to 30 ^F 0 64
SAT.C Supply Air Temp Calib. –30 to 130 dF 64
SAT.T Supply Air Temp Trim –30 to 30 ^F 0 64
RAT.C Return Air Temp Calib. –30 to 130 dF
RAT.T Return Air Temp Trim –30 to 30 ^F 0
CONFIGURATION
CCN CCN Configuration
CCN.A CCN Element Number 1 to 239 1 (not in CCN table) 35, 51
CCN.B CCN Bus Number 0 to 239 0 (not in CCN table) 35, 51
BAUD CCN Baud Rate 1=2400
2=4800
3=9600
4=19200
5=38400
3 (not in CCN table) 35, 51
BROD CCN Broadcast Configuration BRODEFS
B.TIM CCN Time/Date Broadcast Yes/No No CCNBC 51
B.OAT CCN OAT Broadcast Yes/No No OATBC 51
B.GS Global Schedule Broadcast Yes/No No GSBC 40, 51
B.ACK CCN Broadcast Ack'er Yes/No No CCNBCACK 51
SCH.O CCN Schedule Overrides SCHEDOVR
SCH.N Schedule Number 0=Always Occupied
1 to 64=Local Schedule
65 to 99=Global Schedule
0 SCHEDNUM 36, 40, 51
HOL.G Accept Global Holidays Yes/No No HOLIDAYT 51
OV.TL Override Time Limit 0 to 4 hours 1 OTL 51
OV.EX Timed Override Hours 0 to 4 hours 0 OVR_EXT 40, 52
OV.SP SPT Override Enabled Yes/No Yes TIMEOVER 40, 52