99
APPENDIX A — LOCAL DISPLAY AND CCN TABLES (cont)
MODE — CONFIGURATION (cont)
LEGEND
FIOP — Factory-Installed Option
ITEM EXPANSION RANGE UNITS DEFAULT CCN TABLE/SUB-TABLE CCN POINT PAGE NO.
CONFIGURATION (cont)
HMZR Humidimizer Config HMZR CFG 42, 47
REHT Humidimizer Equipped Yes/No No: no Humidi-MiZer FIOP
Yes: Humidi-MiZer FIOP
REHEAT 47, 56
R.DEC Reheat2 Stage Decr. Time 0 to 999 secs 60 RSTAGDEC 47
R.INC Reheat2 Stage Incr. Time 0 to 999 secs 300 RSTAGINC 47
RH.FN Reheat Fan Control Yes/No Yes RHFANCTL 47, 56
RF.LV Reheat2 ODF Fan On Level 0 to 3 2 RHFANLEV 47
RF.ON Reheat2 ODF Fan On Temp 0 to 100 F 93 (20)
93 (24)
85 (28)
RHFANON 47
RF.OF Reheat2 ODF Fan Off Temp 0 to 100 F 83 (20)
88 (24)
80 (28)
RHFANOFF 47
RA.LO Reheat2 OAT Limit A 20 to 70 F 40 OATLRH_A 47
RA.LP Reheat2 SSP Lo Limit A 50 to 100 psig 80 RHSSPL_ A 47
RA.HP Reheat2 SSP Hi Limit A 50 to 100 psig 90 RHSSPH_A 47
RB.LO Reheat2 OAT Limit B, C 20 to 70 F 50 OATLRH_B 47
RB.LP Reheat2 SSP Lo Limit B, C 50 to 100 psig 80 RHSSPL_B 47
RB.HP Reheat2 SSP Hi Limit B, C 50 to 100 psig 90 RHSSPH_B 47
HEAT Heating Configuration HEAT_CFG
HT.TY Type of Heat Installed 0 = No Heat
1 = Gas
2 = Electric
0 (50 series with no
electric heat)
1 (48 series)
2 (50 series with electric
heat)
HEATTYPE 42, 44, 82
N.HTR Number of Heat Stages 1 to 2 1 (48 series 1-phase,
50 series <15kW)
2 (48 series 3-phase,
50 series >=15kW)
NUM_HEAT 44
MRT.H Heat Minimum On Time 60 to 999 sec 120 HMIN_ON 42, 44
MOT.H Heat Minimum Off Time 60 to 999 sec 120 HMIN_OFF 42, 44
H.DEC Heat Stage Decrease Rate 120 to 999 sec 300 HSTAGDEC 43, 44
H.INC Heat Stage Increase Rate 120 to 999 sec 450 HSTAGINC 43, 44
FOD.E Fan-off Delay, Elect Heat 10 to 600 sec 30 ELEC_FOD 44
FOD.G Fan-off Delay, Gas Heat 45 to 600 sec 45 GAS_FOD 43
HT.LO Heating Lockout Temp 40 to 125 dF 75 OATLHEAT 42
SAT.H SAT Heat Mode Sensing Enable/Disable Disable SAT_HEAT 44
SPT Space Temperature Sensor
HT.PD SPT Heat Demand (+) Level 0.5 to 5 ^F 1 HDEM_POS
HT.ND SPT Heat Demand (–) Level –5 to –0.5 ^F –1 HDEM_NEG
H.LAG Heat Thermal Lag Factor 0 to 5 min 1 HEAT_LAG
ECON Economizer Configuration ECON_CFG
EC.EN Economizer Installed Yes/No No: no FIOP
Yes: FIOP
ECONO 44, 82
E.CTL Economizer Control Type 1=Digital, Position Feedback
2=Digital, Command Feedback
3=Analog Control
1 ECON_CTL 36, 45, 57
EC.MN Econo Minimum Position 0 to 100 % 30 ECONOMIN 44
EC.MX Econo Cool Max Position 0 to 100 % 100 ECONOMAX 44, 45
EH.LO Econo Cool Hi Temp Limit 40 to 100 dF 65 OATLECLH
EL.LO Econo Cool Lo Temp Limit –30 to 50 dF 0 OATLECLL
UEFC Unoccupied Free Cooling 0=Disabled
1=Entire Unoccupied Period
2=PreOccupancy Time
2UEFC_CFG45
FC.TM Free Cool PreOcc Time 1 to 9999 min 120 UEFCTIME 45
FC.LO Free Cool Low Temp Limit 0 to 70 dF 50 OATLUEFC 45
PE.EN Power Exhaust Installed Yes/No No: no FIOP
Yes: FIOP
PE_ENABL 45, 82
PE.1 PE Stage1 Econo Position 10 to 100 % 40 PE1_POS 45
PE.2 PE Stage2 Econo Position 10 to 100 % 75 PE2_POS 45
EN.SW Enthalpy Switch 0=No Switch
1=Normally Open
2=Normally Closed
0: no FIOP
1: FIOP
ENTHLCFG 38
E.TRV Economizer Travel Time 5 to 300 sec 150 ECONOTRV
E.MXB Bottom Stage Max Econo 0 to 100 % 50 ECONMAXB
E.MXM Middle Stage Max Econo 1 to 100 % 35 ECONMAXM
E.MXT Top Stage Max Econo 0 to 100 % 25 ECONMAXT
E.DBD Economizer PID Deadband 0 to 25 % 3 ECONBAND
EC.P Economizer PID — kP 0.0 to 99.9 sec 2.5 ECONO_P
EC.I Economizer PID — kI 0.0 to 99.9 sec 0.1 ECONO_I
EC.D Economizer PID — kD 0.0 to 99.9 sec 1 ECONO_D
EC.DT Economizer PID — rate 10.0 to 180.0 sec 15 ECONO_DT