98
APPENDIX A — LOCAL DISPLAY AND CCN TABLES (cont)
MODE — CONFIGURATION (cont)
LEGEND
FIOP — Factory-Installed Option
ITEM EXPANSION RANGE UNITS DEFAULT CCN TABLE/ SUB-TABLE CCN POINT PAGE NO.
CONFIGURATION (cont)
COOL (cont)
CIR.B Circuit B 42
CS.B1 B1 Current Sensing Enable/Disable Enable B1_SENSE 55
B1.FN B Circuit Level 1 Fans 0 to 7 No Humidi-MiZer FIOP
4
Humidi-MiZer FIOP
1
CIR_B_1
B2.FN B Circuit Level 2 Fans 0 to 7 No Humidi-MiZer FIOP
6 (20)
2 (24, 28)
Humidi-MiZer FIOP
3 (20)
2 (24, 28)
CIR_B_2
B3.FN B Circuit Level 3 Fans 0 to 7 No Humidi-MiZer FIOP
6
Humidi-MiZer FIOP
3
CIR_B_3
CIR.C Circuit C 42
CS.C1 C1 Current Sensing Enable/Disable Disable C1_SENSE 55
C1.FN C Circuit Level 1 Fans 0 to 7 0 CIR_C_1
C2.FN C Circuit Level 2 Fans 0 to 7 0 CIR_C_2
C3.FN C Circuit Level 3 Fans 0 to 7 0 CIR_C_3
SST Low Suction Control LOW SUCTION CONTROL
SST.O Suction OK Temperature 10 to 50 dF 18 SSTOK
SST.1 Low Suction — Level 1 10 to 50 dF 20 SSTLEV1 55
SST.2 Low Suction — Level 2 5 to 50 dF 15 SSTLEV2 55
SST.3 Low Suction — Level 3 0 to 50 dF 10 SSTLEV3 55
OFC Outdoor Fan Control OUTDOOR FAN CONTROL 42
OFC.3 OFC3 Enable. CCH Disable Yes/No Yes OFC3_CTL 56
0.MXP Fan Lev0 Max Pressure 100 to 500 psig 200 LEV0MAXP
1.MXP Fan Lev1 Max Pressure 100 to 500 psig 450 LEV1MAXP
2.MNP Fan Lev2 Min Pressure 100 to 500 psig 200 LEV2MNP
2.ON Fan Lev2 On Temperature 0 to 100 F no Humidi-MiZer FIOP:
55 (20)
45 (24-28)
Humidi-MiZer FIOP:
68 (20)
61 (24)
61 (28)
LEV2ON
2.OFF Fan Lev2 Off Temperature 0 to 100 F no Humidi-MiZer FIOP:
50 (20)
40 (24-28)
Humidi-MiZer FIOP:
57 (20)
57 (24)
57 (28)
LEV2OFF
2.MXP Fan Lev2 Max Pressure 100 to 500 psig 400 LEV2MAXP
3.MNP Fan Lev3 Min Pressure 100 to 500 psig 250 LEV3MINP
3.ON Fan Lev3 on Temperature 0 to 100 F no Humidi-MiZer FIOP:
65
Humidi-MiZer FIOP:
88 (20)
68 (24)
68 (28)
LEV3ON
3.OFF Fan Lev3 Off Temperature 0 to 100 F no Humidi-MiZer FIOP:
55
Humidi-MiZer FIOP:
78 (20)
62 (24)
62 (28)
LEV3OFF