APPENDIX A — LOCAL DISPLAY AND CCN TABLES (cont)
MODE — CONFIGURATION
LEGEND
FIOP — Factory-Installed Option
ITEM EXPANSION RANGE UNITS DEFAULT CCN TABLE/SUB-TABLE CCN POINT PAGE NO.
CONFIGURATION SERVICE CONFIGURATION
DISP
Display Configuration DISPLAY
METR Metric Display On/Off Off DISPUNIT 39
LANG Language Selection 0=English
1=Spanish
2=French
3=Portuguese
0LANGUAGE39
PROT Password Enable Enable/Disable Enable PASS_EBL 39
PSWD Service Password 0000 to 9999 1111 PASSWORD 39
TEST Test Display LEDs On/Off Off DISPTEST 39
UNIT Unit Configuration UNIT
S.DLY Start Up Delay 0 to 600 sec 30 STARTDLY 39
U.CTL Unit Control Type 1=Auto Select
2=Thermostat
3=Space Sensor
2 CTL_TYPE 35, 39, 41,
43, 47
T.CTL Thermostat Control Type 0=Adaptive
1=1 Stage Y1
2=2 Stage Y1
0 STATTYPE 38, 39, 41
OC.FN Fan On When Occupied Yes/No Yes OCC_FAN 39, 41, 43
IDF.F Shut Down on IDF Failure Yes/No Yes FATALFAN 40, 56
EC.EN Economizer Installed Yes/No No: no FIOP
Yes: FIOP
ECONO 40, 41
FN.SW Fan Status Switch 0=No Switch
1=Normally Open
2=Normally Closed
0: no FIOP
1: FIOP
FANSTCFG 40, 56, 82
FL.SW Filter Status Switch 0=No Switch
1=Normally Open
2=Normally Closed
0: no FIOP
1: FIOP
FILSTCFG 40, 82
FS.SW Fire Shutdown Switch 0=No Switch
1=Normally Open
2=Normally Closed
0: no FIOP
1: FIOP
SHTDNCFG 38, 40
RM.SW Remote Occupancy Switch 0=No Switch
1=Normally Open
2=Normally Closed
0 REMOCCFG 38, 40
SAT.T SAT Settling Time 10 to 900 sec 240 SAT_SET 40, 42
SAT.H SAT Heat Mode Sensing Enable/Disable Disable SAT_HEAT 40, 44
RAT.S RAT Sensor On SPTO Input Yes/No No RAT_SPTO 40, 82
RH.S
RH Sensor ON OAQ Input Yes/No No RH_OAQ 35, 38, 40,
47, 82
RH.SW Space Humidity Switch 0=No Switch
1=Normal Open
2=Normal Closed
0: no Humidi-MiZer FIOP
1: Humidi-MiZer FIOP
HUMSTCFG 35, 38, 40,
47, 82
TCS.C Temp Cmp Strt Cool Factr 0 to 60 mins 0 TCSTCOOL 40, 51
TCS.H Temp Cmp Strt Heat Factr 0 to 60 mins 0 TCSTHEAT 40, 41
COOL Cooling Configuration COOL_CFG
N.CIR Number of Circuits 1 to 3 2 NUM_CIRC 56
N.A Compressors on Circuit A 1 to 2 1 A_COMPS 56
MRT.C Compressor Min On Time 120 to 999 sec 180 MIN_ON 41, 42
MOT.C Compressor Min Off Time 300 to 999 sec 300 MIN_OFF 41, 42
RST.C Runtime to Reset Strikes 120 to 999 sec 300 MIN_ON_S
C.DEC Cool Stage Decrease Rate 120 to 999 sec 300 STAGEDEC 41, 42
C.INC Cool Stage Increase Rate 120 to 999 sec 450 STAGEINC 41, 42
FOD.C Fan-off Delay, Mech Cool 0 to 600 sec 60 COOL_FOD
CA.LO Circuit A Lockout Temp 0 to 100 dF 0 OATLCMPA 41
CB.LO Circuit B Lockout Temp 0 to 100 dF 0: no Humidi-MiZer FIOP
Humidi-MiZer FIOP:
0
OATLCMPB 41
CC.LO Circuit C Lockout Temp 0 to 100 dF 0 OATLCMPC 41
ALM.N Alert Each Strike Yes/No Yes ALM_NOW 52
SAT Supply Air Temperature
SA.PD SAT Cool Demand (+) Level 0.5 to 10 ^F 1 SAT_POS
SA.ND SAT Cool Demand (–) Level –10 to –0.5 ^F –1 SAT_NEG
SAT.U Minimum SAT Upper Level 35.0 to 65.0 dF 58 SATMIN_H
SAT.L Minimum SAT Lower Level 35.0 to 65.0 dF 48 SATMIN_L
SPT Space Temperature
CL.PD SPT Cool Demand (+) Level 0.5 to 5 ^F 1 DEM_POS
CL.ND SPT Cool Demand (–) Level –5 to –0.5 ^F –1 DEM_NEG
C.LAG Cool Thermal Lag Factor 0 to 5 min 1 COOL_LAG
CIR.A Circuit A 42
CS.A1 A1 Current Sensing Enable/Disable Disable (1-phase)
Enable (3-phase)
A1_SENSE 55
CS.A2 A2 Current Sensing Enable/Disable Disable A2_SENSE
A1.FN A Circuit Level 1 Fans 0 to 7 1: No Humidi-MiZer FIOP
(20, 24)
5: No Humidi-MiZer FIOP
(28)
1: Humidi-MiZer FIOP
CIR_A_1
A2.FN A Circuit Level 2 Fans 0 to 7 No Humidi-MiZer FIOP
3 (20)
2 (24, 28)
Humidi-MiZer FIOP
3 (20)
2 (24, 28)
CIR_A_2
A3.FN A Circuit Level 3 Fans 0 to 7 No Humidi-MiZer FIOP
3 (20, 24)
7 (28)
Humidi-MiZer FIOP
3
CIR_A_3