2
GENERAL
Staged Air Volume (SAV™)
Indoor Fan Speed System
The Staged Air Volume (SAV) system utilizes a Fan Speed control
board and Variable Frequency Drive (VFD) to automatically ad-
just the indoor fan motor speed in sequence with the unit’s ventila-
tion, cooling and heating operation. Per ASHRAE 90.1-2016 and
IECC
1
-2015 standards, during the first stage of cooling operation
the SAV system will adjust the fan motor to provide 66% of the
design airflow rate for the unit. When the call for the second stage
of cooling is required, the SAV™ system will allow the design air-
flow rate for the unit established (100%). During the heating
mode, the SAV system will allow total design airflow rate (100%)
operation. During ventilation mode, the SAV system will operate
the fan motor at 66% of full speed.
Figures 1, 2 and 3 show the VFDs used for the SAV indoor fan
speed system.
Fig. 1 — ACH550 Variable Frequency Drive (VFD)
Fig. 2 — ACS320 Variable Frequency Drive (VFD)
Fig. 3 — ACH580 Variable Frequency Drive (VFD)
Identifying Factory Option
This supplement only applies to units that meet the criteria de-
tailed in Table 1. If the unit does not meet that criteria, discard this
document.
NOTE: See Fig. 4 and 5 for examples of typical Model Number
Nomenclature.
NOTE: 48/50LC units are not covered in this document; VFDs are
standard equipment on belt drive LC units. VFD instructions for
the 48/50LC series are found in the Service and Maintenance
Instructions for the LC base units.
1. Third-party trademarks and logos are the property of their respective
owners.
Table 1 — Model Size/VFD Option Indicator
MODEL/SIZES
POSITION IN
MODEL NUMBER
VFD FIOP
INDICATOR
48/50TC / 07-30 17 G-M
50TCQ / 07-24 17 G-M
48/50HC / 07-28 17 G-M
50HCQ / 07-12 17 G-M
40RUA / 07-30 9T
40RUS / 08-30 9T
40RUQ / 07-25 9T