VFD PARAMETERS
The parameters for the VFDs are listed in the following tables
Table 19 — ACS320 VFD common parameters for 48/50
units with electromechanical controls
Table 20 — ACS320 Parameters for 48/50 units with
electromechanical controls
Table 21 — ACS320 VFD common parameters for 48/50
units with I/O Flex controls
Table 22 — ACS320 Parameters for 48/50 units with
I/O Flex controls
Table 23 — ACS320 VFD common parameters for 40RU
units with electromechanical controls
Table 24 — ACS320 Parameters for 40RU units with
electromechanical controls
Table 25 — ACS320 VFD common parameters for 40RU
units with I/O Flex controls
Table 26 — ACS320 Parameters for 40RU units with
I/O Flex controls
Table 27 — ACH550/580 VFD common parameters for
48/50 units with electromechanical controls
Table 28 — ACH550/580 Parameters for 48/50 units with
electromechanical controls
Table 29 — ACH550/580 VFD Parameters for 40RU
Units with VFD Fan Speed Relay Board
Table 30 — ACH550/580 Parameters for 40RU units with
I/O Flex controls
Table 31 — ACH550/580 common parameters for 48/50
units with ComfortLink controls
Table 32 — ACH550/580 Parameters for 48/50 units with
ComfortLink controls
Table 19 — ACS320 VFD Common Parameters for 48/50 Units with Electromechanical Controls
PARAMETERS DESCRIPTION SETTING ACS320
9802 COMM PROT Sel Not Selected
9907 Motor Nominal Frequency 60Hz
1001 EXT1 Commands
1102 EXT1/EXT2 Sel
1103 REF 1 Select
1201 Const Speed Sel DI 2,3
1202 Const Speed 1 40Hz
1203 Const Speed 2 60Hz
1204 Const Speed 3 60Hz
1205 Const Speed 4
1401 Relay Output 1 (16) FLT/ALARM
1403 Relay Output 3 Not Selected
1501 AO1 Content Sel
1601 Run Enable
1608 N/A
1611 Parameter View 3
2007 Minimum Frequency 0.0 HZ
2008 Maximum Frequency 60HZ
2101 Start FCN (1) Auto
2102 Stop FCN (1) Coast
2201 ACCEL/DECEL (0) Not Sel
2202 ACCEL 30s
2203 DECEL 30s
2603 IR COMP Volt 0 volts
2606 Switching Freq 4 HZ
3102 Trial Time 300.0s
3103 Delay Time 6.0s
3104 AR Overcurrent (1) Enabled
5101 FBA Type
5201 Station ID
5202 Baud Rate
5203 Parity
5301 EFB Protocol ID
5302 EFB Station ID
5303 EFB Baud Rate
5304 EFB Parity
5305 EFB CTRL Profile
LEGEND
= HVAC Default, field does not require change.