38
Table 21 — ACS320 VFD Common Parameters for 48/50 Units with I/O Flex Controls
PARAMETERS DESCRIPTION SETTING ACH550
9907 Motor Nominal Frequency 60Hz
1204 Const Speed 3 60Hz
1403 Relay Output 3
1611 Parameter View 3
2007 Minimum Frequency 0HZ
2008 Maximum Frequency 60HZ
2101 Start FCN (1) Auto
2201 ACCEL/DECEL (0) Not Sel
2603 IR COMP Volt 0 volts
2606 Switching Freq 4 HZ
3102 Trial Time 300.0s
3103 Delay Time 6.0s
3104 AR Overcurrent (1) Enabled
5101 FBA Type
5301 EFB Protocol ID
5305 EFB CTRL Profile