53
Table 27 — ACH550/580 VFD Common Parameters for 48/50 Units with Electromechanical Controls
PARAMETERS ACH550 / 580 DESCRIPTION SETTING ACH550 | ACH580
9802 / 58.01 COMM PROT Sel
9907 / 99.08 Motor Nominal Frequency 60Hz
1001 / 20.01 EXT1 Commands
1102 / 19.11 EXT1/EXT2 Sel
1103 / 28.11 REF 1 Select
1201 / 28.22 Const Speed Sel DI2,3 | DI2
1201 / 28.23 Const Speed Sel DI2,3 | DI3
1202 / 28.26 Const Speed 1 40Hz
1203 / 28.27 Const Speed 2 60Hz
1204 / 28.28 Const Speed 3 60Hz
1205 / 28.29 Const Speed 4
1401 / 10.24 Relay Output 1
1403 / 10.30 Relay Output 3 16 FLT/Alarm | FLT/ (14) Fault
1501 / 13.12 AO1 Content Sel
1601 / 20.40 Run Enable
2007 / 30.13 Minimum Frequency 0Hz
2008 / 30.14 Maximum Frequency 60Hz
2101 / 21.19 Start FCN Auto | Automatic
2102 / 21.03 Stop FCN Ramp
2201 / 28.71 ACCEL/DECEL Not Sel | 0
2202 / 28.72 ACCEL 30s
2203 / 28.73 DECEL 30s
2606 / 97.01 Switching Freq 4kHz
5101 / 51.01 FBA Type
5201 / 58.03 Station ID
5202 / 58.04 Baud Rate
5203 / 58.05 Parity
5301 / 58.25 EFB Protocol ID
5302 / 58.03 EFB Station ID
5303 / 58.04 EFB Baud Rate
5304 / 58.05 EFB Parity
5305 / 58.25 EFB CTRL Profile