52
Table 26 — ACS320 VFD Parameters, for 40RU Units with I/O Flex Controls
VFD PARAMETERS PKG ABB ACS320 MOTOR PART NUMBER VFD PART NUMBER DRIVE HP DESC
40RU000203-DATA 40RU000203 HD56FR233 HK30WA523 3 40RU 1.7 HP 230V
40RU000204-DATA 40RU000204 HD56FR463 HK30WA530 3 40RU 1.7 HP 460V
40RU000218-DATA 40RU000218 HD56FE653 HK30WA523 3 40RU 2.4 HP 230V
40RU000219-DATA 40RU000219 HD56FE653 HK30WA530 3 40RU 2.4 HP 460V
40RU000223-DATA 40RU000223 HD60FE656 HK30WA523 5 40RU 3.7 HP 230V
40RU000224-DATA 40RU000224 HD60FE656 HK30WA534 5 40RU 3.7 HP 460V
40RU000206-DATA 40RU000206 HD58FR236 HK30WA523 5 40RU 3.7 HP 230V
40RU000207-DATA 40RU000207 HD58FR236 HK30WA534 5 40RU 3.7 HP 460V
Table 26 — ACS320 VFD Parameters, for 40RU Units with I/O Flex Controls (cont)
LOOKUP VARIABLE VOLTAGE N. AMPS N. HP MAX AMPS CROSS REFERENCE
VFD PARAMETERS 9905 9906 9909 2003 EM_PKG CL_PKG
40RU000203-DATA 230 5.8 1.7 6.7 40RU480130 —
40RU000204-DATA 460 2.9 1.7 3.3 40RU480131 —
40RU000218-DATA 230 7.1 2.4 8.2 40RU480011 —
40RU000219-DATA 460 3.4 2.4 3.9 40RU480012 —
40RU000223-DATA 230 10.8 3.7 12.4 40RU480016 —
40RU000224-DATA 460 4.9 3.7 5.6 40RU480017 —
40RU000206-DATA 230 10.2 3.7 11.7 40RU480133 —
40RU000207-DATA 460 4.8 3.7 5.5 40RU480134 —
LEGEND
— = HVAC Default, field does not require change.