Table 25 — ACS320 VFD Common Parameters for 40RU Units with I/O Flex Controls
PARAMETERS DESCRIPTION SETTING ACS320
9802 COMM PROT Sel BACnet
9907 Motor Nominal Frequency 60Hz
9908 N. RPM 1725
1001 EXT1 Commands (1) DI1
1102 EXT1/EXT2 Sel EXT1
1103 REF 1 Select AI-1
1201 Const Speed Sel DI 2,3
1202 Const Speed 1 40Hz
1203 Const Speed 2 60Hz
1204 Const Speed 3 60Hz
1205 Const Speed 4
1401 Relay Output 1 (16) FLT/ALARM
1403 Relay Output 3
1501 AO1 Content Sel 0103 OUTPUT FREQ
1601 RUN ENABLE DI-1
1608 N/A
1611 Parameter View 3
2007 Minimum Frequency 0.0 HZ
2008 Maximum Frequency 60HZ
2101 Start FCN (1) Auto
2102 Stop FCN (1) Coast
2201 ACCEL/DECEL (0) Not Sel
2202 ACCEL 30s
2203 DECEL 10s
2603 IR COMP Volt 0 volts
2606 Switching Freq 4 KHz
3102 Trial Time 300.0s
3103 Delay Time 6.0s
3104 AR Overcurrent (1) Enable
5101 FBA Type
5201 Station ID
5202 Baud Rate
5203 Parity
5301 EFB Protocol ID
5302 EFB Station ID 1
5303 EFB Baud Rate 76.8kb/s
5304 EFB Parity 8 NONE 1
5305 EFB CTRL Profile
LEGEND
= HVAC Default, field does not require change.