7
Routine Cleaning of NOVATION Condenser Coil
Surfaces
To clean the NOVATION condenser coil, chemicals are
NOT to be used; only water i s approved as the cleaning
solution. Only clean potable water is authorized for
cleaning NOVATION condensers. Carefully remove any
foreign objects or debris a ttached to the coil face or
trapped within the mounting frame and brackets. Using a
high pressure wate r sprayer, purge any soap or industial
cleaners from hose and/or dilution tank prior to wetting
the coil.
Clea n condenser face by spraying the coil core ste adily
and uniformly from top to bottom, directing the spray
straight into or toward the coil face. Do not exceed 900
psig or a 45 degree angle; nozzle must be at least 12 in.
(30 cm) from the coil face. Reduce pressure and use
caution to prevent damage to air centers (fins). Do not
fracture the braze between air centers and refrigerant
tubes. Allow water to drain from the coil core and check
for refrige rant leaks prior to start--up.
NOTE: Please see the NOVATION Condenser Service
section for specific information on the coil.
PERSONAL INJUR Y HAZARD
Failure to follow this caution may result in personal
injury or equipment damage.
Chemical cleaning should NOT be used on the
aluminum NOVATION condenser. Damage to the coil
may oc cur. Only approved cleaning is recommended.
CAUTION
!
Routine Cleaning of Evaporator Coil Sufaces
Monthly cleaning with Totaline environmentally sound
coil cleaner is essential to extend the life of coils. This
cleaner is available from Carrier Replacement parts
division as pa rt number P902--0301 for one ga llon
conta iner, and part number P902 --0305 for a 5 gallon
container. It is recommended that all round tube coil
cle aner as described below. Coil cleaning should be part
of the unit’s regularly scheduled maintenance procedures
to ensure long life of the coil. Failure to clean the coils
may result in reduced durability in the environment.
Avoid the use of
S coil brighteners
S acid cleaning prior to painting
S high pressure washers
S poor quality water for cleaning
Total ine environmentally sound coil cle aner is
non--flammable, hypoallergenic, non--bacteria l, and a
USDA accepted biodegradable agent that will not harm
coil or surrounding com ponents such as electrical wiring,
painted metal surfaces, or insulation. Use of
non--recommended coil cleaners is strongly discouraged
since coil and unit durability could be affected.
Totaline Environmentally Sound Coil Cleaner Appl ication
Equipment
S 2-1/2 gallon garden sprayer
S water rinse with low velocity spray nozzle
PERSONAL INJUR Y HAZARD
Failure to follow this caution may result in corrosion
and damage to the unit.
Harsh chemicals, household bleach or acid or basic
cle aners should not be used to cle an outdoor or indoor
coils of any kind. These cleaners can be very difficult
to rinse out of the coil and can accelerate corrosion at
the fin/tube interface where dissimilar materials are in
contact. If there is dirt below t he surface of the coil,
use the Tot aline environmentally sound coil cleaner as
described above.
CAUTION
!
PERSONAL INJUR Y HAZARD
Failure to follow this caution may result in reduced
unit performance.
High velocity water from a pressure washer, garden
hose, or com pressed air should never be used to clean
a coil. The force of the wter or air jet will bend the fin
edges and icrease airside pre ssure drop.
CAUTION
!
Totaline Environmentally Sound Coil Cleaner application
Instructions
1. Proper eye protection such as safety glasses is recom-
mended during mixing and application.
2. Remove all surface loaded fibers and dirt with a vacu-
um cleaner as described a bove.
3. Thoroughly wet fi nned surfaces with clean water and
a low vel ocity garden hose, being car efull not to bend
fins.
4. Mix Totaline environmentally sound coil cleaner in a
2 1/2 gallon garden spryer according to the instruc-
tions included with the cleaner. The optimum solution
temperature is 100F(38C).
NOTE: Do NOT USE water in excess of 130F(54C),
as the enzymatic activity will be destroyed.
1. Thoroughly apply Totaline environment ally sound
coil cleaner solution to all coil surfaces including
finned area, tube sheets and coil headers.
2. Hold garden sprayer nozzle close to finned areas and
apply cleaner with a vertical, up--and--down motion.
Avoid spraying in horizontal pattern to minimize po-
tential for fin damage.
3. Ensure cleaner thoroughly penetrates deep into finned
areas.
4. Interior and exterior finned areas must be thoroughly
cleaned.
48TC