Return Air
Sampling Tube
C08129
Fig. 22 -- Return Air Sampling Tube Location
Completing Installation of Return Air Smoke
Sensor:
SCREWS
EXHAUST
TUBE
FLEXIBLE
EXTENSION
TUBE
SAMPLING
C08126
Fig. 23 -- Return Air Detector Shipping Position
1. Unscrew t he two screws holding the Return Air
Sensor detec tor plate. (See Fig. 23.) Save the screws.
2. Remove the Return Air Sensor and its detector plate.
3. Rotate the detector plate so the sensor is facing out-
wards and the sampling tube connection i s on the bot-
tom. (See Fig. 24.)
4. Screw the sensor and detector plate into i ts ope rating
position using screws from Step 1. Make sure the
sampling tube connection is on the bot tom a nd the ex-
haust tube is on the top. (See Fig. 23.)
5. Connect the flexible tube on the sampling inlet to the
sampling tube on the basepan.
6. For units with an economizer, the sampling tube is in-
tegra ted into the economizer housing but the connec-
tion of the flexible tubing to the sampling tube is the
same.
C08127
Fig. 24 -- Return Air Sensor Operating Position
FIOP Smoke Detector Wiring and Response
All unit s: FIOP smoke detector is configured to
automatically shut down all unit opera tions when smoke
condition is detected. See Fig. 25, Smoke Detector
Wiring.
Highlight A: JMP 3 is f actory--cut, transferring unit
control to smoke detector.
Highlight B: Smoke detector NC contact set will open on
smoke alarm condition, de--energizing the ORN
conduct or.
48TC