INDICATORS
Normal State
The smoke detector operates in the normal state in the
absence of any trouble conditions and when its sensing
chamber is free of smoke. In the normal sta te, the Power
LED on both the sensor and the controller are on and all
other LEDs a re off.
Alarm
State
The smoke de tector enters the alarm state when the
amount of smoke part iculate in the sensors sensing
chamber exceeds the alarm threshold value. (See Table 3.)
Upon entering the alarm state:
S The sensors Alarm LED and the controller s Alarm LED
turn on.
S The contacts on the controller s two auxiliary relays
switch positions.
S The contacts on the controllers alarm initiation relay
close.
S The controllers remote alarm LED output is activated
(turned on).
S The controllers high impedance multiple fan shutdown
control line is pulled to ground Trouble state.
The SuperDuc t duct smoke detector enters the trouble
state under t he following conditions:
S A sensors cover is removed and 20 minutes pass before
it is properly secured.
S A sensor’s environmental compensation limit is reached
(100% dirty).
S A wiring fault between a sensor and the controller is
detected.
An internal sensor fault is detected upon entering the
trouble state:
S The contacts on the controllers supervisory relay switch
positions. (See Fig. 28.)
S If a sensor troubl e, the sensor s Trouble L ED the
controllers Trouble LED turn on.
S If 100% dirty, the sensors Dirty LED turns on and the
controllers Trouble LED flashes continuously.
S If a wiring fault between a sensor and the controller, the
controllers Trouble LED turns on but not the sensors.
Alarm
Power
Test/reset
switch
Trouble
C07298
Fig. 28 -- Controller Assembly
NOTE: All troubles are latched by the duct smoke
detector. The trouble condition m ust be cleared and then
the duct smoke detector must be reset in order to restore it
to the normal state.
Resetting Alarm and Trouble Condition T
rips:
Manual re set is required to re store smoke de tector systems
to Normal operation. For install ations using two sensors,
the duct smoke detector does not differentiate which
sensor signals an alarm or trouble condition. Check each
sensor for Alarm or Trouble status (indicated by LED).
Clear the condition that has generated the trip at this
sensor. Then reset the sensor by pressing and holding the
reset button (on the side ) for 2 seconds. Verify that the
sensors Alarm and Trouble LEDs are now off. At the
controller, clear its Alarm or Trouble sta te by pre ssing and
holding the manual reset button (on the front cover) for 2
seconds. Verify that the controllers Alarm a nd Trouble
LEDs are now off. Replace all panels.
Troubleshooting
Controller’s Trouble LED is On
1. Check the Trouble LED on each sensor connected to
the c ontroller. If a sensors Trouble LED is on, de-
termine the cause and make the necessary repairs.
2. Check the wiring between the sensor and the control-
ler. If wiring is loose or missing, repair or replace as
required.
Controller’s Trouble LED is
Flashing
1. One or both of the sensors is 100% dirty.
2. Determine which Dirty LED is flashing then clean
that sensor assembly as described in the detector
cleaning section.
Sensor s Trouble LED is
On
1. Check the sensors Dirty LED. If it is flashing, the
sensor is dirty and m ust be cleaned.
2. Check the sensors cover. If it is loose or missing, se-
cure t he cover to the sensor housing.
3. Replace sensor assembly.
Sensor s Power LED is
Off
1. Check the controllers Power LED. If it is off, de-
termine why the controller does not have power and
make the necessary repairs.
2. Check the wiring between the sensor and the control-
ler. If wiring is loose or missing, repair or replace as
required.