Table 21 RTU--MP Controller Inputs and Outputs
POINT NAME
BACnet OBJECT
NAME
TYPE OF I/O
CONNECTION PIN
NUMBERS
INPUTS
Space Temperature Sensor sptsens AI (10K Thermistor) J 2 0 --- 1 , 2
Supply Air Temperature sat AI (10K Thermistor) J 2 --- 1 , 2
Local Outside Air Temperature Sensor oatsens AI (10K Thermistor) J 2 --- 3 , 4
Space Temperature Offset Pot sptopot AI (100K Potentiometer) J 2 0 --- 3
Indoor Air Quality iaq A I ( 4 --- 2 0 m a ) J 4 --- 2 , 3
Outdoor Air Quality oaq A I ( 4 --- 2 0 m a ) J 4 --- 5 , 6
Safety Chain Feedback safety DI (24 VAC) J 1 --- 9
Compressor Safety compstat DI (24 VAC) J 1 --- 2
Fire Shutdown firedown DI (24 VAC) J 1 --- 1 0
Enthalpy Switch enthalpy DI (24 VAC) J 2 --- 6 , 7
Humidistat Input Status humstat DI (24 VAC) J 5 --- 7 , 8
CONFIGURABLE INPUTS*
Space Relative Humidity sprh A I ( 4 --- 2 0 m a )
J4---2,3 or J4---5,6
Outside Air Relative Humidity oarh A I ( 4 --- 2 0 m a )
Supply Fan Status fanstat DI (24 VAC)
J 5 --- 1 , 2 o r J 5 --- 3 , 4 o r
J5 5,6 or J5---7,8
Filter Status filtstat DI (24 VAC)
Remote Occupancy Input remocc DI (24 VAC)
OUTPUTS
Economizer Commanded Position econocmd 4 --- 2 0 m a J 2 --- 5
SupplyFanRelayState sf DO Relay (24VAC , 1A) J 1 --- 4
Compressor 1 Relay State comp_1 DO Relay (24VAC , 1A) J 1 --- 8
Compressor 2 Relay State comp_2 DO Relay (24VAC , 1A) J 1 --- 7
Heat Stage 1 Relay State heat_1 DO Relay (24VAC , 1A) J 1 --- 6
Heat Stage 2 Relay State heat_2 DO Relay (24VAC , 1A) J 1 --- 5
Po wer Exhaust Relay State aux_2 DO Relay (24VAC , 1A) J 1 1 --- 3
Dehumidification Relay State humizer DO Relay (24VAC, 1A) J 1 1 --- 7 , 8
LEGEND
AI --- A n a l o g I n p u t
AO --- A n a l o g O u t p u t
DI --- D i s c r e t e I n p u t
DO --- Discrete Output
* These inputs (if installed) take the place of the default input on the specific channel according to schematic.
P a r a l l e l p i n s J 5 --- 1 = J 2 --- 6 , J 5 --- 3 = J 1 --- 1 0 , J 5 --- 5 = J 1 --- 2 a r e u s e d f o r f i e l d --- i n s t a l l a t i o n .
Refer to the input configuration and accessory sections for more detail.
NOTE: Refer to RTU--MP Controls, Start-Up, Operation,
and Troubleshooting Instructions (Form 48--50H--T--2T)
for complete configuration of RTU--MP, operating
sequence s and troubl eshooting information. Refer to
RTU--MP 3rd Party Integration Guide for details on
configura tion and troubleshooting of connected networks.
Have a copy of these manuals available at unit sta rt--up.
The RTU--MP controlle r requires the use of a Carrier
space sensor. A standard ther mostat cannot be used with
the RTU--MP system.
Supply Air Temperature (SAT) Sensor On
FIOP--equipped 48TC unit, the unit is supplied with a
supply--air temperature (SAT) sensor (33ZCSENSAT).
This sensor is a tubular probe type, approx 6--inches (12.7
mm) in length. It is a nominal 10--k ohm thermistor. See
Table 15 for temperature --resistance characteristic.
The SAT is factory--wired. The SAT probe is wire--tied to
the supply--air opening (on the horizontal opening end) in
its shipping position. Remove the sensor for installation.
Re--position the sensor in the flange of the supply--air
opening or in the supply air duct (as required by local
codes). Drill or punch a 1/2--in. hole in the flange or duct.
Use two field--supplied, self--drilling screws to secure the
sensor probe in a horizonta l orientation. See Fig. 42.
Outdoor Air Temperature (OAT) Sensor The OAT is
fact ory--mounted in the EconoMi$er 2 (FIOP or
accessory). It is a nominal 10k ohm thermistor attached to
an eyelet mounting ring. See Table 15 for
temperature--resistance characteristic.
EconoMi$e r 2 The RTU--MP control is used with
EconoMi$er2 (option or accessory) for outdoor air
management. The damper position is controlled directly
by the RTU--MP control; EconoMi$er 2 has no internal
logic device.
48TC