Fig. 10 — Base Unit Dimensions — 50AW,AY060
NOTES:
1. Weights include economizer or outdoor air damper.
2. Center of Gravity.
3. Unit clearances:
Top of Units: No Overhang
Condenser Coil: 4
-0
[1219]
Economizer Side: 6
-0
[1219]
Heat Side: 4
-0
[1219]
Filter Access Side: 15
-0
[4572]
(For Removal of Evaporator Coil)
4. For smaller service and operational clearance, con-
tact Carrier Application Engineering Department.
5. Bottom ducts designed to be attached to accessory
roof curb. If unit is mounted on dunnage, it is recom-
mended the ducts must be supported by cross
braces as done on accessory roof curb.
6. Base unit weights include outdoor air hoods and filters (indoor fan motor is not
included). Add indoor motor, FIOPs and accessories for total operating weight.
7. VAV motor weights include indoor motor, VFD, VFD transducer and associated
wiring.
8. Dimensions in [ ] are in millimeters, kilograms or kilowatts.
9. For side-supply/return applications, a single return and supply ductwork connec-
tion is recommended for covering all three return and all three supply openings.
The entire area around the duct openings is available for a 1.5
duct flange
attachment.
BASE UNIT WEIGHTS
(See Note 6) lb (kg)
060
50AW/AY
7363 (3340)
UNIT SIZE
CENTER OF GRAVITY
% OF TOTAL WEIGHT
AT EACH CORNER
ft-in. Millimeters
A B A B1234
50AW/AY060
10-3
5
/
8
3-8
5
/
8
3139 1133 20.1 19.6 29.7 30.6