20
Table 4 – Dry Coil Air Delivery* -- Horizontal -- Unit 50EZ -- A30-- 60 Series A
UNIT
MOTOR
SPEED
WIRE
COLOR
EXTERNAL STA TIC PRESSURE (IN. W.C.)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
50EZ---A30
Low Blue CFM 741 638 547 415 --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
M e d --- L o w Pink CFM 973 887 823 733 665 538 451 --- --- --- --- --- ---
Medium Red CFM 1088 1023 954 881 800 723 658 563 461
M e d --- H ig h
1
Orange CFM 1140 1064 996 915 840 758 687 564 480
High Black CFM 1202 1140 1082 1015 961 881 810 732 631
50EZ---A36
Low Blue CFM 1234 1168 1093 1021 961 894 825 759 687
M e d --- L o w Pink CFM 1290 1223 1154 1090 1027 977 894 828 762
Medium
1
Red CFM 1354 1290 1226 1158 1102 1046 981 918 843
M e d --- H ig h Orange CFM 1606 1546 1489 1430 1371 1316 1258 1208 1140
High Black CFM 1630 1580 1517 1463 1407 1339 1277 1210 1131
50EZ---A42
Low Blue CFM 1295 1234 1182 1126 1075 1016 955 898 857
M e d --- L o w Pink CFM 1345 1282 1235 1194 1140 1095 1027 974 921
Medium Red CFM 1505 1452 1413 1358 1323 1282 1234 1169 1130
M e d --- H ig h
1
Orange CFM 1545 1492 1449 1411 1362 1313 1278 1231 1188
High Black CFM 1705 1643 1607 1568 1518 1483 1448 1404 1360
50EZ---A48
Low Blue CFM 1402 1351 1311 1263 1224 1172 1136 1080 1041
M e d --- L o w Pink CFM 1457 1404 1367 1318 1284 1233 1197 1144 1104
Medium
1
Red CFM 1736 1695 1642 1601 1553 1512 1465 1427 1381
M e d --- H ig h Orange CFM 2149 2111 2062 2026 1980 1945 1905 1864 1793
High Black CFM 2344 2306 2259 2203 2141 2070 1991 1902 1803
50EZ---A60
Low Blue CFM 1445 1389 1341 1281 1236 1189 1139 1072 1027
M e d --- L o w Pink CFM 1678 1635 1602 1558 1513 1474 1438 1404 1349
Medium
1
Red CFM 1927 1893 1858 1824 1791 1759 1720 1689 1640
M e d --- H ig h Orange CFM 2131 2088 2065 2013 1982 1941 1888 1860 1785
High Black CFM 2461 2409 2339 2286 2192 2140 2062 1968 1874
* Air delivery values are without air filter and are for dry coil (See Wet Coil Pressure Drop Table).
1
Factory ---shipped cooling speed
NOTE: Deduct field---supplied air filter pressure drop and wet coil pressure drop to obtain external static pressure available for ducting.
Shaded areas indicate speed/static combinations that are not permitted for dehumidification speed.
NOTE: Deduct 10% for 208 volt operation.
50EZ--A