EasyManua.ls Logo

Carrier 50EZ-A30 - Page 23

Carrier 50EZ-A30
34 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
23
Table 5 -- Dry Co il Air Delivery -- Downflow Discharge (Cont)
UNIT
MOTOR
SPEED
WIRE
COLOR
EXTERNAL STATIC PRESSURE (IN. W.C.)
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.0
50EZ----A60
Low Blue
CFM 1479 1436 1387 1346 1298 1253 1206 1160 1114 1061
WATTS 224 239 247 262 270 284 300 307 319 330
BHP 0.24 0.26 0.26 0.28 0.29 0.30 0.32 0.33 0.34 0.35
MedLow Pink
CFM 1841 1796 1761 1724 1690 1651 1616 1578 1527 1478
WATTS 425 434 453 460 476 485 501 508 525 542
BHP 0.46 0.47 0.49 0.49 0.51 0.52 0.54 0.54 0.56 0.58
Medium
1
Red
CFM 2045 2009 1970 1933 1905 1868 1829 1802 1751 1683
WATTS 569 579 597 607 623 639 648 665 674 663
BHP 0.61 0.62 0.64 0.65 0.67 0.69 0.69 0.71 0.72 0.71
MedHigh Orange
CFM 2178 2148 2105 2073 2036 2002 1967 1919 1845 1751
WATTS 674 691 703 717 733 743 758 754 734 701
BHP 0.72 0.74 0.75 0.77 0.79 0.80 0.81 0.81 0.79 0.75
High Black
CFM 2480 2432 2375 2322 2236 2161 2085 2006 1917 1808
WATTS 1029 1012 995 975 941 908 869 836 796 751
BHP 1.10 1.09 1.07 1.05 1.01 0.97 0.93 0.90 0.85 0.81
*Air delivery values are without air filter and are for dry coil (See Wet Coil Pressure Drop table).
1
Factory--shipped cooling speed
NOTE: Deduct field--supplied air filter pressure drop and wet coil pressure drop to obtain external static pressure available for ducting.
Shaded areas indicate speed/static combinations that are not permitted.