35
To use the keypad when working with Setpoints, System and
Advanced Settings, Checkout tests and Alarms:
1. Navigate to the desired menu.
2. Press the (Enter) button to display the first item in the
currently displayed menu.
3. Use the and buttons to scroll to the desired parame-
ter.
4. Press the (Enter) button to display the value of the
currently displayed item.
5. Press the button to increase (change) the displayed
parameter value.
6. Press the button to decrease (change) the displayed
parameter value.
NOTE: When values are displayed, pressing and holding the or
button causes the display to automatically increment or decre-
ment.
1. Press the (Enter) button to accept the displayed value
and store it in nonvolatile RAM. “CHANGE STORED”
displays.
2. Press the (Enter) button to return to the current menu
parameter.
3. Press the (Menu Up/Exit) button to return to the previ-
ous menu.
Menu Structure
Table 10 illustrates the complete hierarchy of menus and pa-
rameters for the EconoMi$er
®
X system.
The Menus in display order are:
•STATUS
SETPOINTS
SYSTEM SETUP
ADVANCED SETUP
•CHECKOUT
•ALARMS
NOTE: Some parameters in the menus use the letters MA or
MAT, indicating a mixed air temperature sensor location before
the cooling coil. This unit application has the control sensor locat-
ed after the cooling coil, in the fan section, where it is designated
as (Cooling) Supply Air Temperature or SAT sensor.
Setup and Configuration
Before being placed into service, the W7220 Economizer mod-
ule must be set up and configured for the installed system.
The setup process uses a hierarchical menu structure that is
easy to use. Press the and arrow buttons to move forward
and backward through the menus and press the (Enter) but-
ton to select and confirm setup item changes.
Time-Out and Screensaver
When no buttons have been pressed for 10 minutes, the LCD
displays a screen saver, which cycles through the Status items.
Each Status items displays in turn and cycles to the next item
after 5 seconds.
IMPORTANT: Table 10 illustrates the complete hierar-
chy. Your menu parameters may be different depending
on your configuration.
For example if you do not have a DCV (CO
2
) sensor,
then none of the DCV parameters appear and only MIN
POS will display. If you have a CO
2
sensor, the DCV
MIN and DCV MAX will appear.
IMPORTANT: During setup, the economizer module is
live at all times.

Table of Contents