DRY COIL AIR DELIVERY* — VERTICAL DISCHARGE (DEDUCT 10% FOR 208 V)
UNIT
50HS
MOTOR
SPEED
230 AND 460 V VERTICAL DISCHARGE
External Static Pressure (in. wg)
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
018
Low
Watts 230 225 220 210 195 170 —————
Cfm760745725695640540—————
High
Watts ————270235200————
Cfm————850700450————
024
Low
Watts 280 275 265 255 250 245 240 ————
Cfm820810755700660600560————
Med
Watts 365 360 350 345 340 330 320 310 300 — —
Cfm 1025 1010 975 940 900 850 800 720 630 — —
High
Watts — — 490 480 470 460 445 430 410 390 380
Cfm — — 1300 1255 1200 1150 1080 1005 915 790 620
030
Low
Watts ———————————
Cfm———————————
Med
Watts — 365 360 360 350 350 —————
Cfm — 1060 1020 980 935 880 —————
High
Watts ————490485475460450430—
Cfm————1270 1220 1170 1100 1020 920 —
036
Low
Watts 520 495 474 458 495 425 —————
Cfm 1375 1335 1290 1244 1200 1146 —————
Med
Watts 575 560 535 510 480 460 440 425 — — —
Cfm 1520 1490 1450 1440 1380 1300 1200 1080 — — —
High
Watts ————650614575540510480—
Cfm————1560 1500 1380 1280 1170 1060 —
042
Low
Watts 424 416 408 396 384 373 333 312 — — —
Cfm 1288 1227 1205 1168 1116 1064 949 851 — — —
Med
Watts 557 549 571 509 506 480 465 430 394 358 —
Cfm 1566 1536 1485 1440 1388 1326 1253 1124 995 366 —
High
Watts 836 783 757 721 697 660 623 589 555 511 465
Cfm 2010 1955 1915 1851 1747 1654 1540 1415 1305 1134 852
048
Low
Watts 1080 1040 1020 970 910 840 785 730 680 620 540
Cfm 2100 2090 2080 2060 1980 1900 1810 1710 1590 1450 1200
High
Watts 1230 1190 1125 1060 1010 940 880 820 760 710 660
Cfm 2390 2340 2280 2210 2150 2030 1900 1770 1630 1480 1300
060
Low
Watts 890 850 810 780 740 710 660 630 580 — —
Cfm 2500 2410 2330 2260 2170 2080 1970 1860 1700 — —
High
Watts — — — 1000 960 910 870 830 790 750 —
Cfm — — — 2480 2370 2250 2120 2000 1850 1690 —
*Air delivery values are based on operating voltage of 230 v or
460 v, dry coil, without filter or electric heater. Deduct wet coil, filter,
and electric heater pressure drops to obtain external static pressure
available for ducting.
NOTES:
1. Do not operate the unit at a cooling airflow that is less than
350 cfm for each 12,000 Btuh of rated cooling capacity. Indoor coil
frosting may occur at airflows below this point.
2. Dashes indicate portions of table that are beyond the blower motor
capacity or are not recommended.