Dimensions
SIZES 018-036 WITHOUT BASE RAIL
UNIT
ELECTRICAL
CHARACTERISTICS
UNIT WT CORNER WT (Lb/Kg) UNIT HEIGHT (in./mm) DIMENSION (in./mm)
LbKgABCD E F
50HS018 208/230-1-60 233 106 66/30 45/20 95/43 42/19 24.1/613 18.2/462
50HS024 208/230-1-60 256 117 68/31 46/21 97/44 45/20 24.1/613 18.2/462
50HS030 208/230-1-60, 208/230-3-60 268 122 66/30 58/26 91/41 53/24 24.1/613 18.2/462
50HS036 208/230-1-60, 208/230-3-60, 460-3-60 288 131 71/32 63/29 96/44 58/26 28.1/714 22.2/563
UNIT
CENTER OF GRAVITY (in./mm)
XYZ
50HS018 20.7/525 19.2/487 10.6/270
50HS024 20.4/517 19.3/491 10.6/270
50HS030 20.3/515 20.1/510 10.6/270
50HS036 20.1/511 20.2/513 12.4/314
REQ’D CLEARANCES FOR SERVICING in. (mm)
Indoor Coil Access Side ...................30(762)
Control Box Access Side ..................30(762)
(Except for NEC requirements)
Unit Top ...........................36(914)
Side Opposite Ducts ....................30(762)
REQ’D CLEARANCES TO COMBUSTIBLE MAT’L in. (mm)
Unit Top ...............................0
Duct Side of Unit ..........................0
Side Opposite Ducts ........................0
Bottom of Unit ...........................0
Vertical Discharge, First 12 in. (305) of Supply Duct .....1(25)
NEC REQ’D CLEARANCES in. (mm)
Between Units, Control Box Side .............42(1067)
Unit and Ungrounded Surfaces, Control Box Side ......36(914)
Unit and Block or Concrete Walls and Other
Grounded Surfaces, Control Box Side ..........42(1067)
LEGEND
CG Center of Gravity
MAT’L Material
NEC National Electrical Code
REQ’D Required
NOTES:
1. Clearances must be maintained to prevent recirculation of air from
outdoor-fan discharge.
2. Dimensions in ( ) are in mm.
5