Dimensions (cont)
SIZES 018-036 WITH OPTIONAL BASE RAIL
UNIT
ELECTRICAL
CHARACTERISTICS
UNIT WT CORNER WT (Lb/Kg) UNIT HEIGHT (in./mm) DIMENSION (in./mm)
Lb Kg A B C D E F
50HS018 208/230-1-60 268 122 70/32 50/23 100/45 48/22 27.43/697 21.50/546
50HS024 208/230-1-60 276 125 73/33 51/23 102/46 50/23 27.43/697 21.50/546
50HS030 208/230-1-60, 208/230-3-60 288 131 71/32 63/29 96/44 58/26 27.43/697 21.50/546
50HS036 208/230-1-60, 208/230-3-60, 460-3-60 308 140 76/35 68/31 101/46 63/29 31.43/798 25.50/648
UNIT
CENTER OF GRAVITY (in./mm)
XYZ
50HS018 20.4/518 19.4/493 12.9/329
50HS024 20.2/513 19.5/495 12.9/329
50HS030 20.1/511 20.2/513 12.9/329
50HS036 20.0/508 20.3/515 14.7/373
REQ’D CLEARANCES FOR SERVICING — in. (mm)
Indoor Coil Access Side .....................30(762)
Control Box Access Side ....................30(762)
(Except for NEC requirements)
Unit Top .............................36(914)
Side Opposite Ducts ......................30(762)
REQ’D CLEARANCES TO COMBUSTIBLE MAT’L — in. (mm)
Unit Top .................................0
Duct Side of Unit ............................0
Side Opposite Ducts ..........................0
Bottom of Unit .............................0
Vertical Discharge, First 12 in. (305) of Supply Duct .......1(25)
NEC REQ’D CLEARANCES — in. (mm)
Between Units, Control Box Side ...............42(1067)
Unit and Ungrounded Surfaces, Control Box Side ........36(914)
Unit and Block or Concrete Walls and Other
Grounded Surfaces, Control Box Side ............42(1067)
LEGEND
CG — Center of Gravity
MAT’L — Material
NEC — National Electrical Code
REQ’D — Required
NOTES:
1. Clearances must be maintained to prevent recirculation of air from
outdoor-fan discharge.
2. Dimensions in ( ) are in mm.
6