Electrical data
UNIT
50HS
V-PH-Hz
COMPRESSOR OFM IFM
POWER SUPPLY
FUSE OR HACR BRK
AWG60C
MIN
WIRE
MAX WIRE
LENGTH
RLA LRA FLA FLA MCA Max
018 208/230-1-60 10.4 49.0 0.7 1.8 15.5 25 14 75
024 208/230-1-60 11.2 61.0 1.4 2.0 17.4 25 12 80
030
208/230-1-60 14.4 82.0 1.4 2.6 22.0 30 12 80
208/230-3-60 10.4 65.5 1.4 2.6 17.0 25 14 55
036
208/230-1-60 18.0 96.0 1.4 2.8 26.7 40 10 90
208/230-3-60 11.4 75.0 1.4 2.8 18.5 25 12 65
460-3-60 5.4 40.0 0.8 1.4 9.0 10 14 100
042
208/230-1-60 20.4 102.0 1.4 4.0 30.9 50 8 100
208/230-3-60 14.0 91.0 1.4 4.0 22.9 30 10 85
460-3-60 6.4 42.0 0.8 2.0 10.8 15 14 100
048
208/230-1-60 26.4 129.0 2.1 5.0 40.1 60 6 100
208/230-3-60 15.0 99.0 2.1 5.0 25.9 40 10 75
460-3-60 8.2 49.5 1.1 2.3 13.7 20 14 100
060
208/230-1-60 32.1 169.0 2.1 6.2 32.4 50 8 95
208/230-3-60 19.3 123.0 2.1 6.2 32.4 50 8 95
460-3-60 10.0 62.0 1.1 3.2 16.8 25 12 100
LEGEND
AWG American Wire Gage
CSA Canadian Standards Association
FLA Full Load Amps
HACR Heating, Air Conditioning and Refrigeration
IFM Indoor-Fan Motor
LRA Locked Rotor Amps
MCA Minimum Circuit Amps
NEC National Electrical Code
OFM Outdoor-Fan Motor
RLA Rated Load Amps
NOTES:
1. In compliance with NEC requirements for multimotor and combina-
tion load equipment (refer to NEC Articles 430 and 440), the overcur-
rent protective device for the unit shall be fuse or HACR breaker. The
CSA units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is
greater than 2%.
Use the following formula to determine the percent
of voltage imbalance.
% Voltage Imbalance
max voltage deviation from average voltage
= 100 x
average voltage
Example: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
452 + 464 + 455
Average Voltage =
3
1371
=
3
= 457
Determine maximum deviation from average voltage.
(AB) 457 452=5v
(BC) 464 457=7v
(AC) 457 455=2v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
7
% Voltage Imbalance = 100 x
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maxi-
mum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.
22