SIZES 042-060 WITHOUT BASE RAIL
UNIT
ELECTRICAL
CHARACTERISTICS
UNIT WT CORNER WT (Lb/Kg)
Lb Kg A B C D
50HS042,048 208/230-1-60, 208/230-3-60, 460-3-60 359 163 89/40 81/37 113/51 76/35
50HS060 208/230-1-60, 208/230-3-60, 460-3-60 373 170 92/42 85/39 116/53 80/36
UNIT
CENTER OF GRAVITY (in./mm)
XYZ
50HS042,048 19.7/500 20.5/522 15.0/381
50HS060 19.7/499 20.6/523 15.0/381
REQ’D CLEARANCES FOR SERVICING in. (mm)
Indoor Coil Access Side ...................30(762)
Control Box Access Side ..................30(762)
(Except for NEC requirements)
Unit Top ...........................36(914)
Side Opposite Ducts ....................30(762)
REQ’D CLEARANCES TO COMBUSTIBLE MAT’L in. (mm)
Unit Top ...............................0
Duct Side of Unit ..........................0
Side Opposite Ducts ........................0
Bottom of Unit ...........................0
Vertical Discharge, First 12 in. (305) of Supply Duct .....1(25)
NEC REQ’D CLEARANCES in. (mm)
Between Units, Control Box Side .............42(1067)
Unit and Ungrounded Surfaces, Control Box Side ......36(914)
Unit and Block or Concrete Walls and Other
Grounded Surfaces, Control Box Side ..........42(1067)
LEGEND
CG Center of Gravity
MAT’L Material
NEC National Electrical Code
REQ’D Required
NOTES:
1. Clearances must be maintained to pre-
vent recirculation of air from outdoor-fan
discharge.
2. Dimensions in ( ) are in mm.