ELECTRIC HEATER PACKAGES — 208/240 V, SINGLE-PHASE,
SINGLE POINT WIRING CONNECTIONS
UNIT
50HS
ELECTRIC HEAT/
ACCESSORY KIT
CPHEATER---A00
ELECTRIC HEAT
(kW)*
HEATER
FLA
MIN CIRCUIT
AMPACITY FOR
WIRE SIZING
MAX FUSE
OR HACR
BRKR
MOCP
208 V 240 V 208 V 240 V 208 V 240 V 208 V 240 V 208 V 240 V
018
001 3.75 5.0 18.1 20.8 38.1 41.5 40 45 — —
002 5.60 7.5 27.1 31.3 49.3 54.6 50 60 — —
015 7.50 10.0 36.1 41.7 60.6 67.6 — — 70 70
024
001 3.75 5.0 18.1 20.8 40.0 43.4 45 45 — —
002 5.60 7.5 27.1 31.3 51.2 56.5 60 60 — —
015 7.50 10.0 36.1 41.7 62.5 69.5 — — 70 70
030
001 3.75 5.0 18.1 20.8 44.9 48.4 50 50 — —
014 5.60 7.5 27.1 31.3 56.2 61.4 60 — — 70
015 7.50 10.0 36.1 41.7 67.5 74.5 — — 70 80
016 11.30 15.0 54.1 62.0 90.0 99.9 — — 90 100
036
001 3.75 5.0 18.1 20.8 49.3 52.7 60 60 — —
014 5.60 7.5 27.1 31.3 60.5 65.8 — — 70 70
015 7.50 10.0 36.1 41.7 71.8 78.8 — — 80 80
016 11.30 15.0 54.1 62.0 94.3 104.2 — — 100 110
017 15.00 20.0 72.2 83.3 116.9 130.5 — — 125 150
042
001 3.75 5.0 18.1 20.8 53.5 56.9 60 60 — —
014 5.60 7.5 27.1 31.3 64.7 70.0 — — 70 80
015 7.50 10.0 36.1 41.7 76.0 83.0 — — 80 90
016 11.30 15.0 54.1 62.0 98.5 108.4 — — 100 110
017 15.00 20.0 72.2 83.3 121.2 135.0 — — 125 150
048
013 3.75 5.0 18.1 20.8 62.7 66.1 — — 80 80
014 5.60 7.5 27.1 31.3 73.9 79.2 — — 90 90
015 7.50 10.0 36.1 41.7 85.2 92.2 — — 100 100
016 11.30 15.0 54.1 62.0 107.7 117.6 — — 110 125
017 15.00 20.0 72.2 83.3 130.4 144.3 — — 150 150
060
013 3.75 5.0 18.1 20.8 71.0 74.5 — — 90 100
014 5.60 7.5 27.1 31.3 82.3 87.5 — — 100 100
015 7.50 10.0 36.1 41.7 93.6 100.5 — — 100 110
016 11.30 15.0 54.1 62.0 116.1 125.9 — — 125 150
017 15.00 20.0 72.2 83.3 138.7 152.6 — — 150 175
LEGEND
FLA — Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
MOCP — Maximum Overcurrent Protection (fuses or HACR-type
circuit breaker)
NEC — National Electrical Code
*Electric heat capacity (kW) is based on heater voltages of 208 v or
240 v. If power distribution voltage to units varies from rated heater
voltage, see Multiplication Factors table on page 21.
NOTE: In compliance with NEC requirements for multimotor and com-
bination load equipment (refer to NEC Articles 430 and 440), the over-
current protective device for the unit shall be fuse or HACR breaker.
19