ELECTRIC HEATER PACKAGES 208/240 V, SINGLE-PHASE,
SINGLE POINT WIRING CONNECTIONS
UNIT
50HS
ELECTRIC HEAT/
ACCESSORY KIT
CPHEATER---A00
ELECTRIC HEAT
(kW)*
HEATER
FLA
MIN CIRCUIT
AMPACITY FOR
WIRE SIZING
MAX FUSE
OR HACR
BRKR
MOCP
208 V 240 V 208 V 240 V 208 V 240 V 208 V 240 V 208 V 240 V
018
001 3.75 5.0 18.1 20.8 38.1 41.5 40 45
002 5.60 7.5 27.1 31.3 49.3 54.6 50 60
015 7.50 10.0 36.1 41.7 60.6 67.6 70 70
024
001 3.75 5.0 18.1 20.8 40.0 43.4 45 45
002 5.60 7.5 27.1 31.3 51.2 56.5 60 60
015 7.50 10.0 36.1 41.7 62.5 69.5 70 70
030
001 3.75 5.0 18.1 20.8 44.9 48.4 50 50
014 5.60 7.5 27.1 31.3 56.2 61.4 60 70
015 7.50 10.0 36.1 41.7 67.5 74.5 70 80
016 11.30 15.0 54.1 62.0 90.0 99.9 90 100
036
001 3.75 5.0 18.1 20.8 49.3 52.7 60 60
014 5.60 7.5 27.1 31.3 60.5 65.8 70 70
015 7.50 10.0 36.1 41.7 71.8 78.8 80 80
016 11.30 15.0 54.1 62.0 94.3 104.2 100 110
017 15.00 20.0 72.2 83.3 116.9 130.5 125 150
042
001 3.75 5.0 18.1 20.8 53.5 56.9 60 60
014 5.60 7.5 27.1 31.3 64.7 70.0 70 80
015 7.50 10.0 36.1 41.7 76.0 83.0 80 90
016 11.30 15.0 54.1 62.0 98.5 108.4 100 110
017 15.00 20.0 72.2 83.3 121.2 135.0 125 150
048
013 3.75 5.0 18.1 20.8 62.7 66.1 80 80
014 5.60 7.5 27.1 31.3 73.9 79.2 90 90
015 7.50 10.0 36.1 41.7 85.2 92.2 100 100
016 11.30 15.0 54.1 62.0 107.7 117.6 110 125
017 15.00 20.0 72.2 83.3 130.4 144.3 150 150
060
013 3.75 5.0 18.1 20.8 71.0 74.5 90 100
014 5.60 7.5 27.1 31.3 82.3 87.5 100 100
015 7.50 10.0 36.1 41.7 93.6 100.5 100 110
016 11.30 15.0 54.1 62.0 116.1 125.9 125 150
017 15.00 20.0 72.2 83.3 138.7 152.6 150 175
LEGEND
FLA Full Load Amps
HACR Heating, Air Conditioning and Refrigeration
MOCP Maximum Overcurrent Protection (fuses or HACR-type
circuit breaker)
NEC National Electrical Code
*Electric heat capacity (kW) is based on heater voltages of 208 v or
240 v. If power distribution voltage to units varies from rated heater
voltage, see Multiplication Factors table on page 21.
NOTE: In compliance with NEC requirements for multimotor and com-
bination load equipment (refer to NEC Articles 430 and 440), the over-
current protective device for the unit shall be fuse or HACR breaker.
19