11
Performance data-Standard PSC indoor motor
COOLING EXTENDED PERFORMANCE TABLE
HEATING EXTENDED PERFORMANCE TABLE -10–20
HEATING EXTENDED PERFORMANCE TABLE 30–60
*At 75°F entering dry bulb—Tennessee Valley Authority [TVA] rating conditions; all others at 80°F entering dry bulb.
See Legend and Notes on page 17.
50JZ024 COOLING PERFORMANCE TABLE
Temp (F)
Outdoor Air
Entering
Condenser
Evaporator Air—CFM/BF
700/0.10 800/0.14 900/0.18
Evaporator Air — Ewb (F)
62 63* 67 72 62 63* 67 72 62 63* 67 72
75
TC 24.1 25.1 26.6 28.6 25.1 25.7 27.4 29.1 25.6 26.1 27.8 29.5
SHC 21.3 17.6 18.2 14.6 23.2 18.9 19.4 15.2 24.5 19.9 20.3 15.7
kW 1.86 1.86 1.87 1.89 1.87 1.87 1.88 1.89 1.87 1.87 1.88 1.90
85
TC 22.8 23.7 25.1 26.9 23.7 24.2 25.7 27.4 24.1 24.6 26.1 27.7
SHC 20.6 17.2 17.4 13.9 22.3 18.1 18.5 14.4 23.4 19.1 19.3 14.9
kW 2.05 2.06 2.06 2.08 2.06 2.06 2.06 2.08 2.06 2.06 2.07 2.09
95
TC 21.5 22.2 23.3 24.7 22.1 22.5 23.8 25.1 22.5 22.8 24.1 25.4
SHC 19.9 16.5 16.4 12.8 21.2 17.3 17.3 13.3 22.1 18.1 18.0 13.7
kW 2.26 2.26 2.27 2.29 2.26 2.27 2.28 2.29 2.27 2.27 2.28 2.30
105
TC 18.5 19.3 20.0 21.1 19.0 19.4 20.4 21.5 19.4 19.6 20.6 21.7
SHC 17.6 14.8 14.4 11.1 18.7 15.4 15.1 11.6 19.3 16.0 15.7 11.9
kW 2.54 2.53 2.55 2.57 2.55 2.53 2.56 2.58 2.55 2.54 2.56 2.58
115
TC 17.0 17.4 18.4 19.4 17.5 17.7 18.7 19.8 17.9 17.9 18.9 19.8
SHC 16.6 13.9 13.6 10.4 17.5 14.5 14.3 10.8 17.9 15.1 14.8 11.0
kW 2.80 2.80 2.81 2.82 2.80 2.81 2.82 2.80 2.81 2.81 2.82 2.82
125
TC 15.4 15.7 16.7 17.6 16.0 15.9 16.9 17.8 16.4 16.1 17.1 17.8
SHC 15.3 13.0 12.8 9.6 16.0 13.7 13.5 9.9 16.4 14.3 14.0 10.1
kW 3.09 3.11 3.10 3.11 3.06 3.12 3.13 3.14 3.10 3.12 3.13 3.14
50JZ024
Return
Air (F db)
CFM (Standard Air)
Air Temperature Entering Outdoor Coil (F db at 70% rh)
-100 101720
60
700
TC
7.1
6.5 9.5 8.7 12.0 10.9 14.0 12.7 14.9 13.4
kW
1.53 1.61 1.69
1.76 1.79
800
TC
7.1
6.6 9.7 8.9 12.2 11.2 14.3 13.0 15.2 13.7
kW
1.57 1.63 1.68 1.75 1.77
900
TC
7.3
6.7 9.8 9.1 12.4 11.4 14.4 13.2 15.5 14.0
kW
1.59 1.64 1.69 1.74 1.76
70
700
TC
6.2
5.7 8.8 8.0 11.3 10.4 13.3 12.1 14.3 12.9
kW
1.72 1.79 1.87
1.93 1.95
800
TC
6.4
5.9 9.0 8.3 11.6 10.6 13.6 12.4 14.6 13.2
kW
1.73 1.79 1.86 1.91 1.93
900
TC
6.6
6.1 9.2 8.4 11.8 10.9 13.9 12.6 14.9 13.4
kW
1.75 1.80 1.86 1.90 1.92
80
700
TC
5.5
5.1 8.0 7.4 10.5 9.7 12.6 11.5 13.5 12.2
kW
1.86 1.96 2.05
2.13 2.16
800
TC
5.6
5.2 8.2 7.5 10.9 9.9 12.9 11.8 13.9 12.5
kW
1.90 1.97 2.04 2.11 2.12
900
TC
5.8
5.3 8.4 7.7 11.0 10.1 13.2 12.0 14.2 12.8
kW
1.91 1.98 2.04 2.10 2.11
50JZ024
Return
Air (F db)
CFM (Standard Air)
Air Temperature Entering Outdoor Coil (F db at 70% rh)
30 40 47 50 60
60
700
TC
18.1
15.8 21.7 21.7 24.4 24.4 25.3 25.3 27.9 27.9
kW
1.90 1.99 2.09 2.12 2.22
800
TC
18.5
16.2 22.1 22.1 24.7 24.7 25.3 25.3 28.1 28.1
kW
1.86 1.94 2.04 2.05 2.14
900
TC
18.9
16.6 22.4 22.4 25.0 25.0 25.5 25.5 28.3 28.3
kW
1.82 1.92 2.01 2.01 2.11
70
700
TC
17.6
15.4 21.1 21.1 23.9 23.9 24.8 24.8 27.7 27.7
kW
2.03 2.16 2.29 2.34 2.47
800
TC
17.9
15.7 21.4 21.4 24.4 24.4 25.2 25.2 28.6 28.6
kW
2.00 2.13 2.24 2.28 2.42
900
TC
18.3
16.0 21.8 21.8 24.7 24.7 25.5 25.5 28.9 28.9
kW
1.98 2.10 2.22 2.24 2.36
80
700
TC
16.7
14.7 20.5 20.5 23.3 23.3 24.1 24.1 27.8 27.8
kW
2.27 2.37 2.51 2.56 2.76
800
TC
17.4
15.2 20.8 20.8 23.7 23.7 24.6 24.6 28.5 28.5
kW
2.17 2.31 2.46 2.50 2.70
900
TC
17.6
15.5 21.2 21.2 24.1 24.1 24.9 24.9 28.7 28.7