16
Performance data (cont)-Standard PSC indoor motor
COOLING EXTENDED PERFORMANCE TABLE
HEATING EXTENDED PERFORMANCE TABLE -10–20
HEATING EXTENDED PERFORMANCE TABLE 30–60
*At 75°F entering dry bulb—Tennessee Valley Authority [TVA] rating conditions; all others at 80°F entering dry bulb.
See Legend and Notes on page 17.
50JZ060 COOLING PERFORMANCE TABLE
Temp (F)
Outdoor Air
Entering
Condenser
Evaporator Air—CFM/BF
1750/0.07 2000/0.08 2250/0.09
Evaporator Air — Ewb (F)
62 63* 67 72 62 63* 67 72 62 63* 67 72
75
TC 59.2 59.6 64.7 68.6 60.7 60.5 65.1 68.9 61.8 60.5 68.6 68.8
SHC 54.7 43.8 46.1 36.2 58.6 46.2 48.2 37.3 60.8 48.3 50.1 38.1
kW 4.55 4.75 4.62 4.67 4.72 4.98 4.85 4.89 4.94 5.25 5.14 5.17
85
TC 56.4 56.3 61.8 66.2 57.7 56.9 62.3 66.3 59.0 57.2 62.3 69.8
SHC 53.6 42.4 44.8 35.4 57.3 44.6 47.3 36.6 58.9 46.7 49.4 37.4
kW 4.97 5.21 5.08 5.12 5.11 5.45 5.31 5.33 5.35 5.70 5.59 5.61
95
TC 53.3 52.8 58.3 63.2 54.7 52.9 58.9 63.5 56.0 53.4 58.9 66.8
SHC 52.3 40.7 43.2 34.3 54.7 42.7 46.0 35.6 56.0 45.0 48.2 36.6
kW 5.41 5.72 5.57 5.60 5.49 5.98 5.79 5.83 5.78 6.21 6.04 6.10
105
TC 50.3 49.4 54.5 59.7 51.7 49.9 55.1 59.9 52.9 50.0 55.2 60.5
SHC 50.3 39.1 41.6 33.0 51.7 41.6 44.3 34.3 52.9 43.6 46.5 35.4
kW 5.90 6.24 6.10 6.13 6.24 6.46 6.31 6.35 6.42 6.72 6.56 6.62
115
TC 47.5 45.6 50.6 55.6 48.7 46.2 51.1 55.7 49.7 46.2 51.3 55.7
SHC 47.5 37.4 40.0 31.6 48.7 39.9 42.6 32.8 49.7 42.0 45.2 33.9
kW 6.47 6.80 6.65 6.69 7.00 7.02 6.84 6.90 7.08 7.27 7.07 7.17
125
TC 43.4 41.5 46.4 51.0 45.4 41.9 46.8 51.0 46.2 42.2 26.8 50.5
SHC 41.5 35.7 38.3 29.9 45.4 38.0 40.8 31.1 46.2 40.1 43.1 32.1
kW 7.18 7.34 7.22 7.27 7.25 7.63 7.43 7.48 7.51 7.83 7.65 7.75
50JZ060
Return
Air (F db)
CFM (Standard Air)
Air Temperature Entering Outdoor Coil (F db at 70% rh)
-100 101720
60
1750
TC
12.7
11.7 20.2 18.7 27.6 26.0 32.9 30.0 35.1 31.7
kW
3.61 3.81 4.01
4.15 4.21
2000
TC
12.2
11.3 20.0 18.5 27.7 26.1 33.2 30.2 35.5 32.0
kW
3.70 3.83 3.96 4.05 4.09
2250
TC
12.3
11.4 20.1 18.6 27.9 26.3 33.4 30.5 35.8 32.3
kW
3.70 3.81 3.91 3.98 4.01
70
1750
TC
11.4
10.5 18.8 17.4 26.2 24.6 31.3 28.6 33.5 30.2
kW
4.06 4.23 4.40
4.52 4.57
2000
TC
11.5
10.6 19.0 17.6 26.5 24.9 31.7 28.9 33.9 30.6
kW
4.04 4.18 4.32 4.43 4.47
2250
TC
11.6
10.7 19.1 17.7 26.7 25.2 32.0 29.2 34.3 30.9
kW
4.07 4.18 4.28 4.35 4.38
80
1750
TC
9.3
8.6 16.8 15.5 24.3 22.9 29.6 27.0 31.8 28.7
kW
4.37 4.56 4.75
4.89 4.95
2000
TC
9.5
8.8 17.1 15.8 24.7 23.2 30.0 27.3 32.2 29.1
kW
4.37 4.53 4.69 4.80 4.85
2250
TC
9.8
9.0 17.4 16.1 25.0 23.6 30.3 27.7 32.6 29.4
kW
4.34 4.48 4.62 4.72 4.76
50JZ060
Return
Air (F db)
CFM (Standard Air)
Air Temperature Entering Outdoor Coil (F db at 70% rh)
30 40 47 50 60
60
1750
TC
42.6
37.3 50.5 50.5 55.9 55.9 58.5 58.5 64.4 64.4
kW
4.40 4.55 4.68
4.68 4.81
2000
TC
43.3
37.9 51.0 51.0 57.4 57.4 58.9 58.9 64.1 64.1
kW
4.22 4.40 4.48 4.51 4.59
2250
TC
43.6
38.2 51.4 51.4 57.2 57.2 59.2 59.2 65.4 65.4
kW
4.12 4.28 4.34 4.38 4.48
70
1750
TC
40.9
35.8 49.2 49.2 55.4 55.4 57.9 57.9 65.5 65.5
kW
4.74 4.97 5.17
5.16 5.39
2000
TC
41.4
36.3 49.8 49.8 56.1 56.1 58.6 58.6 65.7 65.7
kW
4.61 4.82 4.99 4.99 5.16
2250
TC
41.9
36.7 50.3 50.3 56.6 56.6 59.1 59.1 65.6 65.6
kW
4.49 4.70 4.85 4.85 4.98
80
1750
TC
39.3
34.5 47.2 47.2 54.0 54.0 56.5 56.5 65.2 65.2
kW
5.14 5.39 5.67
5.69 5.99
2000
TC
39.8
34.9 47.8 47.8 55.0 55.0 57.2 57.2 65.3 65.3
kW
5.01 5.24 5.41 5.49 5.71
2250
TC
40.2
35.3 48.3 48.3 55.4 55.4 57.7 57.7 66.6 66.6
kW
4.91 5.11 5.28 5.34 5.58