The 50JZ units dispose of condensate through a 3/4 in. NPT (19.05
mm) female fitting that exits on the compressor end of the unit.
Condensate water can be drained directly onto the roof in rooftop
installations (where permitted) or onto a gravel apron in ground
level installations. Install a field-supplied condensate trap at end of
condensate connection to ensure proper drainage. Make sure that
the outlet of the trap is at least 1 in. lower than the drain condensate
connection to prevent the drain from overflowing. Prime the trap
with water. When using a gravel apron, make sure it slopes away
from the unit.
If the installation requires draining the condensate water away
from the unit, install a field-supplied 2 -in. (50.8 mm) trap at the
Table 1—Physical Data-Unit 50JZ (50Hz)-English
UNIT SIZE 50JZ024 50JZ030 50JZ036 50JZ048
NOMINAL CAPACITY (ton) 2 2-1/2 3 4
OPERATING WEIGHT (lb.) 299 320 328 355
COMPRESSOR QUANTITY 1
TYPE SCROLL COMPRESSOR
REFRIGERANT R-410A
REFRIGERANT METERING DEVICE Accurater
Refrigerant (R-410A) Quantity (lb.) 6.9 9.6 10.0 12.0
ORIFICE ID (in.) 0.059 0.061 0.067 0.078
ORIFICE OD (in.) 0.032 (2) 0.040 (2) 0.040 (2) 0.046 (2)
OUTDOOR COIL
Rows... Fins/in.
face area (sq. ft.)
2...17
8.5
2...17
10.3
2...17
10.3
2...17
13.5
OUTDOOR FAN
Nominal Airflow (CFM)
Diameter
Motor HP (RPM)
2200
22
1/4...900
2200
22
1/4...900
2200
22
1/4...900
2400
22
1/3...1340
INDOOR COIL
Rows... Fins/in.
face area (sq. ft.)
3...15
3.7
3...15
3.7
4...15
3.7
4...15
4.7
INDOOR BLOWER
Nominal Airflow (CFM)
Size (in.)
Motor (HP)
800
10x10
1/2
1000
10x10
1/4
1200
10x10
1/2
1600
11x10
1
RETURN-AIR FILTERS (in.)*
throwaway
20x20x1 20x20x1 20x24x1 24x30x1
* Required filter sizes shown are based on the larger of the ARI (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of 300
ft/minute for throwaway type or 450 ft/minute for high-capacity type. Air filter pressure drop for non-standard filters must not exceed 0.08 in. wg.
Table 2—Physical Data-Unit 50JZ (50 Hz)-SI
UNIT SIZE 50JZ024 50JZ030 50JZ036 50JZ048
NOMINAL CAPACITY (kW) 7 8.8 10.6 14.1
OPERATING WEIGHT (kg) 135 145 149 161
COMPRESSOR QUANTITY 1
TYPE SCROLL COMPRESSOR
REFRIGERANT R-410A
REFRIGERANT METERING DEVICE Accurater
Refrigerant (R-410A) Quantity (kg) 3.2 4.0 4.2 4.8
ORIFICE ID (mm) 1.55 1.55 1.70 1.93
ORIFICE OD (mm) 0.81 1.02 1.02 1.17
OUTDOOR COIL
Rows... Fins/in.
Face Area (sq. m)
2...659
8.5
2...669
10.3
2...669
10.3
2...669
13.5
OUTDOOR FAN
Nominal Airflow (L/s)
Diameter (mm)
Motor HP (r/s)
1038
558.8
.187...15
1038
558.8
.187...15
1038
558.8
.187...15
1133
558.8
.249...22
INDOOR COIL
Rows... Fins/m.
Face Area (sq. m)
3...590
0.34
3...590
0.34
3...590
0.34
4...590
0.44
INDOOR BLOWER
Nominal Airflow (L/s)
Size (m)
Motor (r/s)
378
0.254x0.254
186...17.9
472
0.254x0.254
373...21.7
566
0.254x0.254
373...21.9
708
0.254x0.254
746...20.5
RETURN-AIR FILTERS (mm)
throwaway
508x508 508x508 508x508 610x762
* Required filter sizes shown are based on the larger of the ARI (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of 91.5
m./min. for throwaway type or 137 m. cu../min. for high-capacity type. Air filter pressure drop for non-standard filters must not exceed 2.03 mm. wg.
9