21
NOMINAL CFM CORRECTIONS
ENTERING AIR CORRECTIONS
LEGEND
*Sensible capacity equals total capacity.
NOTES:
1.
Bold
indicates performance data table conditions.
2. ARI/ISO/ASHRAE 13256-1 uses entering air conditions of Cooling
80.6 F DB/66.2 F WB and Heating 68 F DB/59 F WB and
high fan speed.
3. Discontinued Standards ARI 320, 325, and 330 used entering air
conditions of Cooling 80 F DB/67 F WB and Heating 70 F DB
(bold print).
50KQA,KQD CONSOLE BLOWER PERFORMANCE 60 Hz
NOTES:
1. Fan speed is field adjustable.
2. All airflow is rated at lowest voltage if unit is dual voltage rated, i.e., 208 v for 208-230 v
units.
3. All units ARI/ISO/ASHRAE 13256-1 rated on high fan speed.
4. All units are designed and rated for zero external static pressure (non-ducted) application.
SCFM
(%)
COOLING CORRECTIONS HEATING CORRECTIONS
Total
Cooling
Capacity
Sensible
Cooling
Capacity
Power
Input
Watts
Heat of
Rejection
Heating
Capacity
Power
Input
Watts
Heat of
Absorption
67% 0.951 0.912 0.905 0.946 0.971 1.110 0.856
73% 0.961 0.930 0.924 0.957 0.977 1.088 0.885
80% 0.971 0.947 0.943 0.968 0.982 1.066 0.914
87% 0.980 0.964 0.961 0.978 0.988 1.045 0.941
92% 0.990 0.982 0.981 0.989 0.994 1.023 0.971
100% 1.000 1.000 1.000 1.000 1.000 1.000 1.000
107% 1.011 1.019 1.021 1.012 1.006 0.976 1.031
113% 1.020 1.035 1.038 1.022 1.012 0.956 1.058
COOLING CORRECTIONS HEATING CORRECTIONS
Entering
Air Wet
Bulb F
Total
Cooling
Capacity
Sensible Cooling Capacity Entering Dry Bulb
Heat of
Rejection
Entering
Air Dry
Bulb F
Heating
Capacity
Heat of
Absorption
Power
Input
Watts
70
F DB 75
F DB 80
F DB 80.6
F DB 85
F DB 90
F DB
61
0.910 0.763 1.030 1.242 * * * 0.893 60 1.060 1.047 0.940
64 0.955 0.615 0.881 1.110 1.129 1.266 * 0.948 65 1.030 1.023 0.970
66.2 0.994 0.506 0.773 1.030 1.048 1.184 * 0.982 68 1.008 1.006 0.992
67 1.000
0.466 0.733
1.000
1.018 1.154 1.390
1.000 70 1.000 1.000 1.000
70 1.045 * 0.585 0.852 0.884 1.118 1.312 1.052 75 0.970 0.977 1.030
73 1.090 * 0.436 0.703 0.735 0.970 1.234 1.111 80 0.940 0.953 1.060
DB
Dry Bulb
SCFM
Standard Cubic Feet per Minute
WB
Wet Bulb
50KQA,KQD
RATED
CFM
SCFM
Low Speed High Speed
007
280 240 280
009
280 240 280
012
375 320 375
015
400 350 400
019
430 370 430